Permit: T10CM00905

Parcel: 13734001A


Addresses:

1650 W VALENCIA RD


Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T10CM00905

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
01/23/2012 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
12/09/2010 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) WALL PLUG FOR WATER DISPENSOR IS BEING DELETED
2) HEAT TABLES INSTALLED PER MANUFACTURERS INSTRUCTIONS
3) OK ABOVE CEILING BAKERY/HOT DELI
4) FINISH MAIN BREAKER AND ENCLOSE CHANGE OUT FOR "L4D3"
12/08/2010 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
CASH REGISTERS:
1) WAITING ON LISTING FOR SELF CHECK REGISTERS
2) LEE FROM WALMART IS IN CONTROL OF VDV CABLING
3) ELECTRICIANS CONDUIT RUNS AND SUPPORTS OK
12/06/2010 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) NEW VDV CABLING TO BE PER 725.24, 800.24, 300.11-REMOVE OLD 725.3 AND 800.3
2) SEAL UNUSED RACEWWAY OPENINGS
3) SEAL WALK INS PER 300.7
12/03/2010 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1) PROVIDE MANUFACTURERS INSTRUCTION FOR WIRINF OF HEAT TABLES
2) TY WRAP TO M/C NOT SUPPORTED METHOD
12/02/2010 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) PROVIDE PHYSICAL PROTECTION FOR LFNMC
2) OVER CURRENT PROTECTION FOR PANEL L4D3 SHALL BE PER 215.3
11/30/2010 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
11/12/2010 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
DELI SERVICE:
1) ? ABANDON VDV CABLING 725.3
2) FINISH CASES
LINE UP #3:
1) SUPPORT SEAL TITE PER CODE AND PROVIDE PHYSICAL PROTECTION
2) OK NORTH SIDE AND FLORAL
3) OK WALLS AT FRONT GROCERY PLAN EXCEPT AQUA BAR
11/02/2010 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
11/01/2010 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
10/29/2010 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
10/25/2010 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
10/15/2010 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
10/12/2010 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
10/08/2010 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
ELECTRONICS:
1) BOXES OVER FILLED
SPORTING GOODS:
1) BOXES OVER FILLED
2) SUPPORT POWER POLE
3) RELOCATE M/C LAYING ON GRID
4) OK TEMP USEAGE ELECTRONICS AND SPORTING GOODS
10/07/2010 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
10/06/2010 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
08/30/2010 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED SERVICE ELECTRICIAN ON SITE TO OPEN CASES
2) DO NOT USE UNTIL CLEARED BY ALL INSPECTORS
08/24/2010 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1) NO WORK PROGRESS
2) NO ELECTRICAL CONTRACTOR ON JOB
08/23/2010 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
08/20/2010 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) USE APPROVED SUPPORT METHODS
2) CORDS AND PLUGS STRIPS NOT ALLOWED ABOVE CEILING
08/19/2010 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) ANGLE PULL RACEWAY SPACING
2) OK CHEESE CASE, DAIRY, MEAT COFFINS SEAFOOD PREP AT MEAT PREP SUBJECT TO OTHERS
08/18/2010 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
08/16/2010 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
08/10/2010 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) OK DAIRY CASES, EXCEPT RACK ROOM AND ROLL SEAL DOOR
2) OK MEAT/SEAFOOD FOR TRAINING ONLY-NO PUBLIC USE
3) UNLISTED EQUIPMENT RESPONSIBILITY OF HB1 FOR TRAINING ONLY
4) DISCONNECT TEMP POWER CIRCUITS AFTER TRAINING

SEAFOOD CASE:
1) USE CORRECT SIZED WIRE SPLICE CONNECTORS
08/09/2010 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
08/05/2010 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
08/04/2010 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
07/21/2010 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
07/20/2010 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
07/19/2010 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
07/14/2010 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) INSTALL DISCONNECTING MEANS FOR HEATER NEC 422.31
2) RICK HOLLANDER TO CHECK XFMR AND PANEL IN PHARMACY
3) OK FINAL PHARMACY WITH EXCEPTION OF 2 ITEMS ABOVE
07/13/2010 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
TRAINING ROOM:
1) INDEPENDENT SUPPORTING VDV 300.11-CAMERA
PHOTO LAB:
1) CORDS NOT ALLOWED ABOVE CEILING 400.7 + 8
2) INDEPENDENT SUPPORTING VDV 300.11-CAMERA
3) OK DEVICES
4) NO NEW WORK REAR BATHROOMS-IN WALLS
07/12/2010 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
07/07/2010 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
06/29/2010 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
06/25/2010 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
06/23/2010 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
06/18/2010 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) OK TEMP CEILING FOR BREAK ROOM
2) WILL RE-CHECK AFTER PHASE 1 MOVES