Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T10CM00905
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/23/2012 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 12/09/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) WALL PLUG FOR WATER DISPENSOR IS BEING DELETED 2) HEAT TABLES INSTALLED PER MANUFACTURERS INSTRUCTIONS 3) OK ABOVE CEILING BAKERY/HOT DELI 4) FINISH MAIN BREAKER AND ENCLOSE CHANGE OUT FOR "L4D3" |
|
| 12/08/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* CASH REGISTERS: 1) WAITING ON LISTING FOR SELF CHECK REGISTERS 2) LEE FROM WALMART IS IN CONTROL OF VDV CABLING 3) ELECTRICIANS CONDUIT RUNS AND SUPPORTS OK |
|
| 12/06/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) NEW VDV CABLING TO BE PER 725.24, 800.24, 300.11-REMOVE OLD 725.3 AND 800.3 2) SEAL UNUSED RACEWWAY OPENINGS 3) SEAL WALK INS PER 300.7 |
|
| 12/03/2010 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1) PROVIDE MANUFACTURERS INSTRUCTION FOR WIRINF OF HEAT TABLES 2) TY WRAP TO M/C NOT SUPPORTED METHOD |
|
| 12/02/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) PROVIDE PHYSICAL PROTECTION FOR LFNMC 2) OVER CURRENT PROTECTION FOR PANEL L4D3 SHALL BE PER 215.3 |
|
| 11/30/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 11/12/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* DELI SERVICE: 1) ? ABANDON VDV CABLING 725.3 2) FINISH CASES LINE UP #3: 1) SUPPORT SEAL TITE PER CODE AND PROVIDE PHYSICAL PROTECTION 2) OK NORTH SIDE AND FLORAL 3) OK WALLS AT FRONT GROCERY PLAN EXCEPT AQUA BAR |
|
| 11/02/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 11/01/2010 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 10/29/2010 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 10/25/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 10/15/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 10/12/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 10/08/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* ELECTRONICS: 1) BOXES OVER FILLED SPORTING GOODS: 1) BOXES OVER FILLED 2) SUPPORT POWER POLE 3) RELOCATE M/C LAYING ON GRID 4) OK TEMP USEAGE ELECTRONICS AND SPORTING GOODS |
|
| 10/07/2010 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 10/06/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 08/30/2010 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED SERVICE ELECTRICIAN ON SITE TO OPEN CASES 2) DO NOT USE UNTIL CLEARED BY ALL INSPECTORS |
|
| 08/24/2010 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) NO WORK PROGRESS 2) NO ELECTRICAL CONTRACTOR ON JOB |
|
| 08/23/2010 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 08/20/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) USE APPROVED SUPPORT METHODS 2) CORDS AND PLUGS STRIPS NOT ALLOWED ABOVE CEILING |
|
| 08/19/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) ANGLE PULL RACEWAY SPACING 2) OK CHEESE CASE, DAIRY, MEAT COFFINS SEAFOOD PREP AT MEAT PREP SUBJECT TO OTHERS |
|
| 08/18/2010 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 08/16/2010 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 08/10/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK DAIRY CASES, EXCEPT RACK ROOM AND ROLL SEAL DOOR 2) OK MEAT/SEAFOOD FOR TRAINING ONLY-NO PUBLIC USE 3) UNLISTED EQUIPMENT RESPONSIBILITY OF HB1 FOR TRAINING ONLY 4) DISCONNECT TEMP POWER CIRCUITS AFTER TRAINING SEAFOOD CASE: 1) USE CORRECT SIZED WIRE SPLICE CONNECTORS |
|
| 08/09/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 08/05/2010 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 08/04/2010 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 07/21/2010 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 07/20/2010 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 07/19/2010 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 07/14/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) INSTALL DISCONNECTING MEANS FOR HEATER NEC 422.31 2) RICK HOLLANDER TO CHECK XFMR AND PANEL IN PHARMACY 3) OK FINAL PHARMACY WITH EXCEPTION OF 2 ITEMS ABOVE |
|
| 07/13/2010 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* TRAINING ROOM: 1) INDEPENDENT SUPPORTING VDV 300.11-CAMERA PHOTO LAB: 1) CORDS NOT ALLOWED ABOVE CEILING 400.7 + 8 2) INDEPENDENT SUPPORTING VDV 300.11-CAMERA 3) OK DEVICES 4) NO NEW WORK REAR BATHROOMS-IN WALLS |
|
| 07/12/2010 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 07/07/2010 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 06/29/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 06/25/2010 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 06/23/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 06/18/2010 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK TEMP CEILING FOR BREAK ROOM 2) WILL RE-CHECK AFTER PHASE 1 MOVES |