Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T10CM00905
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/23/2012 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 12/10/2010 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED |
|
| 12/03/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 11/23/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 11/19/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK LIGHTS REDO IN DRY PRODUCE AND DELI 2) OK MAKE UP PANEL "LF" 3) FINISH NEW VDV CABLING AND REMOVE OLD 4) FINISH GROUNDING ELECTRODE FOR TRANSFORMER |
|
| 11/01/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 10/27/2010 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CANCELLED |
|
| 10/19/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 08/04/2010 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 07/21/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) SUPPORT CAMERA CABLING 300.11 2) OK CONNECTIONS AT DAIRY VAULT |
|
| 07/20/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 07/16/2010 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 07/09/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) PROTECT FLEX AND M/C CABLE IN STUDS 2) OK PRIVACY WALLS PHARMACY-AFTER CORRECTIONS |
|
| 07/08/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* PHARMACY: 1) OK MAIN COUNTER WALL AND INTERIOR BATHROOM WALLS 2) FINISH PRIVACY WALL AND DO NOT COVER UNTIL INSPECTED |
|
| 07/07/2010 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* PHARMACY: 1) TRANSFORMER TO MEET TAP RULES OF 240. 2) PROTECT PVC AT BASE PLATES 3) FINISH VDV CABLING IN WALLS 725.24 AND 800.24 FRONT BEDROOM: 1) WATER FOUNTAIN RECEPTS TO BE ACCESSIBLE 2) FIXTURES TO HAVE DISCONNECTING MEANS 410.63 (?) 3) NEED TO OPEN HAND DRYER PHOTO LAB: 1) SUPPORT VDV CABLING 725.24 AND 800.24 2) DO NOT COVER WALLS WITHOUT INSPECTORS APPROVAL TRAINING ROOM: 1) VDV CABLING NOT INSTALLED PER CODE AND INSTRUCTIONS OF INSPECTOR, ALSO CANNOT SUPPORT OFF OF CONDUIT 2) CORDS NOT ALLOWED ABOVE CEILING 400.7 + 8 3) PLEASE PAY REFEE BEFORE NEXT INSPECTION, THIS IS THE 4TH TIME FOR VDV CABLING STARTING WITH NOTICE ON 6/17/10 |
|
| 06/29/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) TRAINING ROOM: FINISH VDV CABLING AND M/C CABLES 2) OK TRAINING ROOM TO OCCUPY, RECALL ABOVE CEILING ON 7/7/10 |
|
| 06/24/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK RECEPT TEMP PHARMACY AND DROPS |
|
| 06/23/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) RECEPT NOT TO BE SUPPORTED OF COVER 406.3 2) SUPPORT ELECTRIC AND VDV ASSOCIATED TO TEMP PHARMACY ABOVE CEILING 3) OLD WIRING, VDV CABLING AND TRASH LAYING ON TILE, POSING SAFETY HAZARDS |
|
| 06/17/2010 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS ROOMS BATHROOMS FRONT STORE & BREAKROOM SECTIONS 725.3 + 24 825.3 + 24 770.3 + 24 760.3 + 24 300.11 WILL APPLY |