Permit: T10CM00905

Parcel: 13734001A


Addresses:

1650 W VALENCIA RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T10CM00905

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/24/2012 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/23/2012 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) OK EM LIGHTING
2) LAST ITEM RACK ROOMS (NOTED ON 12/8/11 INSPECTION SHEET)
3) RECEIVED MONEY ORDER R20378012-5956 FOR $165.00
12/16/2011 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) MET WITH JOHN WENT OVER ITEM TO BE DONE
2) REVIEW AND REPAIR
01/21/2011 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
12/14/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
12/08/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
11/23/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) OK WALLS AQUA BAR
11/19/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
11/18/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
11/17/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
11/16/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) CHECK WORKING CONDITIONS OF EXIT AND EM LIGHTS-HAVE CIRCUITS READY TO TEST (RECEIVING)
2) OK SOUTH SIDE LINE UP #3
3) OK LIGHTS AND RECEPTS BIKE SHOP
4) GRID REMOVED PRODUCE AND DELI COUNTER, NEED RE-INSPECTIONS
11/12/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
11/04/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
11/03/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) OK FROZEN FOOD CASE #1
2) OK LIGHTS SEATING AREA
3) RECEIVED CVHECK #8442 FOR $330.00 FOR PLUMBING AND ELECTRICAL AFTER HOURS INSPECTIONS
11/02/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
11/01/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
10/15/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
10/14/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
10/12/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
10/08/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
10/06/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
10/05/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
09/30/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
09/01/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
08/30/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
08/24/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
08/23/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
08/20/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
08/19/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
08/18/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
CASH REGISTERS:
1) BOXES (459) AND FLEX LAYING ON TILE
2) UNSAFE SPLICE SINGLE CONDUCTORS TO "SE" CABLE NO BOX-OPEN SPLICE ABOVE TILE
CASES:
1) LOOSE FITTINGS
2) PLATES NOT FULLY ATTACHED
3) PROTECT LENMC FROM SHARP METAL EDGES
4) GROUND JUNCTION BOXES
5) FILL UNUSED OPENING
6) FINISH CHEESE CASE
RACK ROOMS:
1) WILL NEED REVISED PANEL AND CONTROL SCHEDULES
2) ? REFG WILL BE RESPONSIBLE FOR LO/TO OF EQUIPMENT
MEAT PREP:
1) MEAT SAW HAS A LABEL INSTALLED IN THE FIELD NOT A FIELD LABEL
08/16/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
08/10/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
08/09/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
MEAT & SEAFOOD:
1. SEAFOOD CASE NOT MADE UP, CANNOT USE SHEETMETAL THREAD SCREWS FOR GROUNDING, USE APPROVED FITTING WITH SEAT TITE
2. VERIFY LISTING FOR MEAT SAW/SLICER
3. NEED LETTER FOR DELETED EQUIPMENT
08/06/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
08/05/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
08/04/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) OPEN WALL IN WEST ALCOVE TO SEE ELECTRIC COVERED WITHOUT INSPECTION FOR WATER MACHINES
2) FRONT CASH WRAPS REDONE WITHOUT INSPECTIONS WILL NEED ABOVE CEILING ACCESS
3) NEED TO SEE BUSS WAYS ABOVE ELECTRONICS
4) DAIRY CASES IN USE WITHOUT INSPECTION CLEARANCES
5) NEED TO INSPECT RACKS FOR NEW WIRING
6) FINISH PREVIOUS ITEMS
07/28/2010 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) CANCELLED BY BRANDON
07/20/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
PHARMACY:
1. VDV LAYING ON GRID - CAMERA NOT SUPPORTED AS PER 300.11, 725.24

DAIRY:
OK STUD FRAME WALLS

*NOTE: SEAL OF CASES 300.7
07/14/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
07/13/2010 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
07/12/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
07/07/2010 ELECTRIC - FINAL Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspectio
06/29/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
06/24/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
06/23/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
06/21/2010 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
06/21/2010 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) OK TEMP USAGE OF BREAKROOM