Permit: T10CM00905

Parcel: 13734001A


Addresses:

1650 W VALENCIA RD


Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T10CM00905

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
10/20/2011 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
12/06/2010 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) 36" DUCT ABOVE PRODUCE PREP OK TO COVER
12/02/2010 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) ALL WELD TESTS (X5) OK, 1ST LAYER OK, OK FOR 2ND LAYER
11/30/2010 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
11/19/2010 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
11/12/2010 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
10/29/2010 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) RTU-55 DUCT OK TO INSULATE
09/01/2010 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
08/05/2010 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
08/04/2010 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
07/20/2010 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
DUCT ABOVE CEILING IN PHARMACY OK TO COVER
07/19/2010 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
1. REMOVE TILES AROUND ALL REGISTERS AT PHARMACY AREA FOR INSPECTION
2. ALL HARD DUCT TO BE MECHANICALLY FASTENED TO REGISTERS AND GRILLS
3. PROVIDE SEISMIC RESTRAINTS TO STRUCTURE ON ALL REGISTERS AND GRILLS
07/15/2010 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
DUCT (RETURN AIR) NOT INSTALLED PER PLAN
PLANS CALL FOR DUCTED RETURN NOT PLENUM RETURN.
SUPPLY DUCT OK TO COVER AT PHARMACY AREA ONLY

MONEY ORDER R202115478367 $150 RECEIVED BY MRAMBER
07/14/2010 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
07/14/2010 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
06/18/2010 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) DUCT ABOVE BREAKROOM OK TO COVER