Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - PROGRESS
Permit Number - T10CM00905
Inspection Description - ELECTRIC - PROGRESS
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/23/2012 | ELECTRIC - PROGRESS | Approved | IVRS - Inspection :* | |
| 01/10/2011 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) WILL NEED THIRD PARTY FIELD EVALUATION FOR NEW GEAR CONNECTIONS BEFORE POWER CLEARANCE 2) WILL NEED GENERATOR PERMIT AND INSPECTIONS BEFORE ENERGIZING 3) WILL NEED TO SCHEDULE AFTER HOURS INSPECTION AFTER #1 TO CLEAR POWER |
|
| 12/14/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* BAKERY: 1) VERIFY INSTRUCTIONS FOR FREEZER DOOR 2) NEED WATER HEATER INSTALLED 3) FIX DOOR HARDWARE PANELS L4D3-SEC 1, 2 AND 3 4) RECEIVED MONEY ORDER FOR $165.00 |
|
| 12/13/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) RECEPT AND CORD PLUG NOT PART OF SELF CHECK CASH WRAP. INSTALLATION TO BE PER 400.7 & 8 SOLUTION IS TO HARDWIRE WITH M/C |
|
| 12/09/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 12/08/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 12/06/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 12/03/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 12/02/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 11/30/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) OK ABOVE CEILING AQUA BAR 2) NEED TO VERIFY LOADS |
|
| 11/23/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) OK FROZEN FOOD CASE #1 2) OK LIGHTS SEATING AREA 3) RECEIVED CHECK #8442 FOR $330.00 FOR PLUMBING AND ELECTRICAL AFTER HOURS INSPECTIONS |
|
| 11/19/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 11/18/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 11/17/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) OK FLOOR VAULTS REFRIDGERATION PVC SLEEVES |
|
| 11/16/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 11/12/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 11/04/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) OK FROZEN FOOD CASE #2 (ELECTRIC) |
|
| 11/03/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 11/02/2010 | ELECTRIC - PROGRESS | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 11/02/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* FROZEN FOOD CASE: 1) LOOSE FITTINGS 2) CLEAN EXCESS DIRT, METAL SHAVINGS AND FOREIGN MATERIAL FROM BOXES 110.12 3) GROUND JUNCTION BOXES 250.148 |
|
| 11/01/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 10/29/2010 | ELECTRIC - PROGRESS | Not ready for Inspection | IVRS - Inspection :* | |
| 10/27/2010 | ELECTRIC - PROGRESS | Not ready for Inspection | IVRS - Inspection :* | |
| 10/25/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) OK RACEWAYS ON RACK ACCROSS RAFTERS FOR REFRIDGERATION 2) PLEASE VERIFY LISTING FOR ROLL SEALS AT WALK-IN BOXES 3) LB COVERS NEED TO BE ACCESSIBLE |
|
| 10/19/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) OK WALLS JANITORS CLOSETS (2) BY PRODUCE COOLER |
|
| 10/15/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 10/14/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 10/12/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* GARDEN CENTER: 1) CLOSE BOXES AND FILL UNUSED OPENINGS 2) BOXES OVER FILLED 3) VERIFY 700.12 (F) 4) OK ELECTRONICS AND SPORTING GOODS |
|
| 10/08/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 10/06/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) IN SECTION 109.6 WORK SHALL NOT BE DONE BEYOND THE POINT OF A PREVIOUS INSPECTION WITHOUT APPROVAL OF THE BDLG OFFICIAL OR HIS AGENT 2) YOU MAY NOT CONTINUE TO WORK WITHOUT OBTAINING INSPECTIONS AND APPROVALS FOR PREVIOUS AREAS |
|
| 10/05/2010 | ELECTRIC - PROGRESS | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CONDUCTOR COLOR TO BE FOR 277 PER 210.5 (C) CITY AMENDMENTS FRONT BATHROOM LIGHTS-DISCONNECT STILL NOT INSTALLED |
|
| 09/30/2010 | ELECTRIC - PROGRESS | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MEET WITH NEW ELECTRICAL CONTRACTOR WENT OVER LIST-FINISH PREVIOUS ITEMS 1ST |
|
| 09/01/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) RECEIVED FIELD EVALUATION REPORT FOR MEAT SLICER/CUTTER FROM ELT-OK MEAT SLICER 2) SUPPORT CONDUIT RACEWAYS TO SMALL MEAT CASE 3) FOR USAGE OF MEAT CASES CONDUIT TO BE COMPLETED BY 9/7/10 OR CASES TO BE SHUT OFF |
|
| 08/30/2010 | ELECTRIC - PROGRESS | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 08/24/2010 | ELECTRIC - PROGRESS | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* |
|
| 08/23/2010 | ELECTRIC - PROGRESS | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* ELECTRONICS: 1) GROUND JUNCTION BOXES 2) MISSING COVER SCREWS TAP BOX 3) SUPPORT FEEDER RACEWAY CORRECTLY 4) PULL BOX ANGLE PULL SPACING 314.28 5) FILL UNUSED OPENINGS IN BOXES 6) SUPPORT POWER POLE AND M/C CABLES 7) DO NOT USE MIDDLE OF AREA BUSS WAY UNTIL CLEARED |
|
| 08/20/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 08/19/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 08/18/2010 | ELECTRIC - PROGRESS | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 08/16/2010 | ELECTRIC - PROGRESS | Denied | IVRS - Inspection : See detailed listing on site.| 999 CASH REGISTRAAS 1. SUPPORT MANUFACTURE WHIPS AS PER M/C CODE 12"+6' + 300.11 2. SUPPORT VDV CABLE OR REMOVE 725.3 + 24, 800.3 + 24, 300.11 3. PLEASE VERIFY LISTING MARKS FOR CASH REGISTRAAS ASSEMBLY. THERE ARE MULTIPOLE ITEMS INTERALY ATTACHED TO UNITS INCLUDES MOTOR FOR CORVER?? AND LIGHTS 4. PLEASE VERIFY CHECKOUT + COOLER LOADS AS NOTE ON E 2.2 BEER + CHEESE CASES: 5. SUPPORT CONDUCTS, FLEX CONDUCTS FMLE AS PER CODES 2. LOOSE FITTINGS 3. SHEET METAL THREADS NOT ALLOWED FOR GRAUDING 4. FILL USED OPENINGS IN BOX DO NOT STOCK CASES DO NOT USE CASES UNTIL APPROVED FOR USE |
|
| 08/10/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 08/09/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 08/06/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection DAIRY WALK-IN: 1. BOXES OVER FILLED 2. PLEASE VERIFY LISTING + LABELS FOR ROLL SEAL DOOR 3. SEAL BOXES PER 300.7 4. GROUND JUNCTION BOXES OK REAR BATH ROOMS DO NOT OCCUPY REFRIGERATION CASSES WITH OUT CLEARENCES |
|
| 08/05/2010 | ELECTRIC - PROGRESS | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 08/04/2010 | ELECTRIC - PROGRESS | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 07/28/2010 | ELECTRIC - PROGRESS | Not ready for Inspection | IVRS - Inspection :* | |
| 07/21/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 07/20/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 07/19/2010 | ELECTRIC - PROGRESS | Not ready for Inspection | IVRS - Inspection :* | |
| 07/12/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 07/09/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 07/08/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 07/07/2010 | ELECTRIC - PROGRESS | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 06/30/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1) OK 2-3/4 AND 1-2" PVC UNDER SLAB PHARMACY 2) PROTECT PVC AT BASE PLATE |
|
| 06/29/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 06/25/2010 | ELECTRIC - PROGRESS | Not ready for Inspection | IVRS - Inspection :* | |
| 06/24/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 06/23/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 06/21/2010 | ELECTRIC - PROGRESS | Not ready for Inspection | IVRS - Inspection :* | |
| 06/21/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 06/18/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 06/17/2010 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* |