Permit: T08CM00558
Permit Details
Status:
Final
Type:
MULTI FAMILY ALTERATION
Address:
1200 N EL DORADO PL 02
Address NEW:
1200 N EL DORADO PL 02
Apply Date:
02/19/2008
Applicant:
COLE, BENJAMIN WILLIAM
Description:
REPAIR:FIRE DAMAGE
Architects:
- COLE, BENJAMIN WILLIAM
Contractors:
- BELFOR U S A GROUP INC
Permit Reviews
Permit Number - T08CM00558
Permit Status: Final
Permit Description: REPAIR:FIRE DAMAGE
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 02/19/2008 | PLANS OK TO SUBMIT - 3RD PARTY | 02/19/2008 | COMPLETED |
| 02/19/2008 | 3RD PARTY REVIEW-COMMERCIAL | 03/18/2008 | COMPLETED |
| 03/18/2008 | POST 3RD PARTY REVIEW | 03/28/2008 | COMPLETED |
| 12/03/2008 | 3RD PARTY REVIEW-REVISION/OTHER | 12/03/2008 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T08CM00558
Permit Status: Final
Permit Description: REPAIR:FIRE DAMAGE
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 02/19/2008 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T08CM00558
Permit Description: REPAIR:FIRE DAMAGE
Total Completed Inspections - 18
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/15/2008 | PLUMBING - ROUGH, SOIL | BBENEDON | Approved | IVRS - Inspection :* |
| 08/14/2008 | PLUMBING - PRE SLAB | BBENEDON | Approved | IVRS - Inspection :* |
| 08/26/2008 | FRAMING | JBURGE | Approved | IVRS - Inspection :* NEED LETTER FROM ARCHITECT STATING THE USE OF WOOD STUDS AS OK INSTEAD OF METAL STUD SYSTEM |
| 09/11/2008 | PLUMBING - ABOVE CEILING | BBENEDON | Approved | IVRS - Inspection :* |
| 09/15/2008 | MECHANICAL - INTERMEDIATE | JMILITEL | Approved | IVRS - Inspection :* OK TO SHEETROCK HARD LIDS DO NOT USE PLUMBERS TAPE TO SUPPORT EXHAUST DUCT |
| 09/17/2008 | SHEET ROCK NAILING | JBURGE | Approved | IVRS - Inspection :* OK TO TAPE THROUGHOUT |
| 10/24/2008 | MECHANICAL - ABOVE CEILING | JMILITEL | Approved | 1. SUITE 240 RELOCATE LIGHTS AND EXIT SIGN BLOCKING ACCESS TO 2 FAN COILS 2. SUITE 200 RELOCATE SEWER VENT & DUCT BLOCKING ACCESS TO 1 FAN COIL 3. PROVIDE BUSHINGS IN ALL FAN COIL KNOCKOUTS 4. I.D ALL FAN COILS OK FOR CEILING TILES |
| 11/24/2008 | ELECTRIC - TEMP POWER FOR TEST | RMORENO | Approved | |
| 11/24/2008 | ELECTRIC - ABOVE CEILING | RMORENO | Approved | |
| 11/24/2008 | ELECTRIC - INTERMEDIATE | RMORENO | Approved | |
| 11/24/2008 | ELECTRIC - FINAL | RMORENO | Approved | 1. BUSHING INSTALLED IN HOUSE PANEL OK 2. GROUNDS 6' APART OK 3. PARALLEL RUNS BONDED OK 4. SERVICE RISER BONDED OK 5. SERVICE CONDUCTORS OK 6. LABELED SERVICE DISCONNECTS OK 7. PLANS FOR WORK OK |
| 11/26/2008 | TEP CLEARANCE - AM | JWEATHER | Approved | RECN CLEARED FOR "OWNERS METER", STE #200, 250 & 260 PER R. MORENO |
| 12/08/2008 | MECHANICAL - FINAL | JMILITEL | Approved | IVRS - Inspection :* |
| 12/08/2008 | PLUMBING - INTERMEDIATE | BBENEDON | Approved | |
| 12/08/2008 | BUILDING ABOVE CEILING | JBURGE | Approved | |
| 12/08/2008 | BUILDING - FINAL | JBURGE | Approved | IVRS - Inspection :* |
| 12/08/2008 | PLUMBING - FINAL | BBENEDON | Approved | IVRS - Inspection :* |
| 12/09/2008 | PERMIT FINALED | BFLORES | Approved |