Permit: T08CM00558

Parcel: 133146610

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
12/08/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
12/04/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. SECURE MINI-SPLIT CONDENSOR ON ROOF
2. LOW VOLTAGE WIRING EXPOSED MUST BE IN CONDUIT
3. SECURE REFER LINES TO BLOCKS
4. USE ONLY PRESSURE TREATED OR REDWOOD
5. I.D ALL CONDENSORS WITH SUITE NUMBER
6. DO NOT USE DUCT TAPE OUTDOORS
7. USE CONTACT CEMENT ON UV RATED ZIP TIES IF NECESSARY
8. A/C 12 & 13 OVERFUSED
9. A/C 4 & 5 OVERFUSED
10. LEVEL A/C UNITS
11. AIR BALANCE OK
12/01/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE AIR BALANCE REPORT
2. PROVIDE ACCESS TO ROOF & ACCESS TO FAN COILS
TO CHECK CORRECTIONS
11/28/2008 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*