Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/08/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 12/04/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. SECURE MINI-SPLIT CONDENSOR ON ROOF 2. LOW VOLTAGE WIRING EXPOSED MUST BE IN CONDUIT 3. SECURE REFER LINES TO BLOCKS 4. USE ONLY PRESSURE TREATED OR REDWOOD 5. I.D ALL CONDENSORS WITH SUITE NUMBER 6. DO NOT USE DUCT TAPE OUTDOORS 7. USE CONTACT CEMENT ON UV RATED ZIP TIES IF NECESSARY 8. A/C 12 & 13 OVERFUSED 9. A/C 4 & 5 OVERFUSED 10. LEVEL A/C UNITS 11. AIR BALANCE OK |
|
| 12/01/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE AIR BALANCE REPORT 2. PROVIDE ACCESS TO ROOF & ACCESS TO FAN COILS TO CHECK CORRECTIONS |
|
| 11/28/2008 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* |