Permit: T08CM00558

Parcel: 133146610

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
11/24/2008 ELECTRIC - INTERMEDIATE Approved
09/15/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. SEPARATE PERMIT FOR COMMON BATHROOMS
OK WALLS AND CEILINGS SEE T07CM01067
2. RECALL FOR DROP CEILINGS AND SERVICE WHEN READY
09/11/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. INSTALL DISCONNECTING MEANS FOR FAN COIL
UNITS #12, #13 --- SEE E2.1 FAN COIL UNITS TO HAVE SEPARATE CIRCUITS PER PLAN
2. FINISH WIRING LIGHT FIXTURES
3. WIRE EXHAUST FANS
4. OK CEILINGS RESTROOMS 209, 105
08/28/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. INSTALL CONNECTOR ON CONTROL WIRING WHERE IT ENTERS AIR HANDLER
2. ENSURE HOME RUNS & INTERCONNECTING CABLE BETWEEN JUNCTION BOXES FOR PATIENT CARE AREAS MEET REQUIREMENTS FOR NEC 517.13
3. OK WALLS
08/26/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
COMPLETE ITEM #1 FROM INSPECTION ON 8/12/08
HAVE COMPLETE BY NEXT INSPECTION TO AVOID
REINSPECTION FEE
08/19/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. USE APPROVED M/C STRAPS NOT EMT
2. SUPPORT M/C 12" OF CAN AND BOXES
3. PLEASE VERIFY #1 FOR ALL UNITS
08/12/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. ALL EXAM ROOMS TO BE WIRED PER NEC 517.13
THIS INCLUDES EXISTING DEVICES
2. SEAL OPEN KNOCKOUTS IN JUNCTION BOXES
3. FASTEN CABLES WITHIN 12" OF BOXES
4. WHAT IS GOING ON WITH POWER FOR RM 408
5. NEED TO ADD 02036 ELECTRIC ABOVE CEILING TO ACTIVITY