Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/24/2008 | ELECTRIC - INTERMEDIATE | Approved | ||
| 09/15/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. SEPARATE PERMIT FOR COMMON BATHROOMS OK WALLS AND CEILINGS SEE T07CM01067 2. RECALL FOR DROP CEILINGS AND SERVICE WHEN READY |
|
| 09/11/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. INSTALL DISCONNECTING MEANS FOR FAN COIL UNITS #12, #13 --- SEE E2.1 FAN COIL UNITS TO HAVE SEPARATE CIRCUITS PER PLAN 2. FINISH WIRING LIGHT FIXTURES 3. WIRE EXHAUST FANS 4. OK CEILINGS RESTROOMS 209, 105 |
|
| 08/28/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. INSTALL CONNECTOR ON CONTROL WIRING WHERE IT ENTERS AIR HANDLER 2. ENSURE HOME RUNS & INTERCONNECTING CABLE BETWEEN JUNCTION BOXES FOR PATIENT CARE AREAS MEET REQUIREMENTS FOR NEC 517.13 3. OK WALLS |
|
| 08/26/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* COMPLETE ITEM #1 FROM INSPECTION ON 8/12/08 HAVE COMPLETE BY NEXT INSPECTION TO AVOID REINSPECTION FEE |
|
| 08/19/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. USE APPROVED M/C STRAPS NOT EMT 2. SUPPORT M/C 12" OF CAN AND BOXES 3. PLEASE VERIFY #1 FOR ALL UNITS |
|
| 08/12/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ALL EXAM ROOMS TO BE WIRED PER NEC 517.13 THIS INCLUDES EXISTING DEVICES 2. SEAL OPEN KNOCKOUTS IN JUNCTION BOXES 3. FASTEN CABLES WITHIN 12" OF BOXES 4. WHAT IS GOING ON WITH POWER FOR RM 408 5. NEED TO ADD 02036 ELECTRIC ABOVE CEILING TO ACTIVITY |