Permit: T08CM00558

Parcel: 133146610

Inspection Status: Approved

Inspection History: ELECTRIC - TEMP POWER FOR TEST

Date Description Inspector Results Comments
11/24/2008 ELECTRIC - TEMP POWER FOR TEST Approved
11/12/2008 ELECTRIC - TEMP POWER FOR TEST Not ready for Inspection IVRS - Inspection :*
1. INSTALL PROTECTIVE BUSHING ON HOUSE PANEL
2. GROUND RODS TO BE MIN. 6' APART
3. GEC INSTALLED IN METAL RACEWAY TO BE BONDED @ BOTH ENDS
4. SERVICE RISERS TO BE BONDED
5. INSTALL SERVICE CONDUCTORS
6. MARK "SERVICE DISCONNECTS"
7. REVISE PLANS FOR SCOPE OF WORK