11/24/2008 ELECTRIC - FINAL Approved 1. BUSHING INSTALLED IN HOUSE PANEL OK
2. GROUNDS 6' APART OK
3. PARALLEL RUNS BONDED OK
4. SERVICE RISER BONDED OK
5. SERVICE CONDUCTORS OK
6. LABELED SERVICE DISCONNECTS OK
7. PLANS FOR WORK OK