Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T08CM00558

Parcel: 133146610

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
10/24/2008 MECHANICAL - ABOVE CEILING Approved 1. SUITE 240 RELOCATE LIGHTS AND EXIT SIGN BLOCKING ACCESS TO 2 FAN COILS
2. SUITE 200 RELOCATE SEWER VENT & DUCT BLOCKING ACCESS TO 1 FAN COIL
3. PROVIDE BUSHINGS IN ALL FAN COIL KNOCKOUTS
4. I.D ALL FAN COILS

OK FOR CEILING TILES
09/11/2008 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*