Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T08CM00039
Permit Details
Apply Date:
01/04/2008
Applicant:
KATH SOSA
Description:
NEW PROTO GYMNASUM
Contractors:
- LLOYD CONSTRUCTION COMPANY INC ,
- TUCSON UNIFIED SCHOOL DIST #1 **C
Permit Reviews
Permit Number - T08CM00039
Permit Status: C of o
Permit Description: NEW PROTO GYMNASUM
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 01/04/2008 | PLANS OK TO SUBMIT - 3RD PARTY | 01/04/2008 | COMPLETED |
| 01/04/2008 | 3RD PARTY REVIEW-COMMERCIAL | 02/06/2008 | COMPLETED |
| 01/29/2009 | 3RD PARTY REVIEW-REVISION/OTHER | 01/30/2009 | COMPLETED |
| 02/06/2008 | POST 3RD PARTY REVIEW | 02/13/2008 | COMPLETED |
| 02/13/2008 | RESUBMITTAL | 02/25/2008 | COMPLETED |
| 02/25/2008 | RESUBMITTAL | 03/14/2008 | COMPLETED |
| 06/11/2008 | 3RD PARTY REVIEW-REVISION/OTHER | 06/12/2008 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T08CM00039
Permit Status: C of o
Permit Description: NEW PROTO GYMNASUM
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 01/04/2008 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: C of o
Permit Number: T08CM00039
Permit Description: NEW PROTO GYMNASUM
Total Completed Inspections - 43
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/20/2008 | STEM WALL/RETAINING WALL | JBURGE | Approved | IVRS - Inspection :* 2 @ MASONRY COLUMN FOOTINGS (M2/M6) 1 @ MASONRY COLUMN FOOTING (M2/F8) * *WEST WALL (W5) FOOTING OF RESTROOM #105; F1 FOOTINGS FOR STAIRS (UP); EAST FOOTING FOR STORAGE WALL #112 OK TO POUR PROGRESS AREAS |
| 11/07/2008 | PLUMBING - ROUGH, SOIL | BBENEDON | Approved | IVRS - Inspection :* |
| 11/24/2008 | MECHANICAL - INTERMEDIATE | JMILITEL | Approved | IVRS - Inspection :* 100 PSI TEST ON HYDRONIC UNDERGROUND PIPING RISER SECTION ONLY. OK TO BACKFILL THIS SECTION. |
| 11/24/2008 | FIRE SPKLR - UG, PIPING, HYDRO | IVR USER | Approved | IVRS - RI canceled |
| 11/25/2008 | PLUMBING - YARD WTR LINE/TEST | BBENEDON | Approved | IVRS - Inspection :* 2 1/2" K AT BUILD SERVICE W/BRAZED JOINT |
| 12/04/2008 | PLUMBING - ROOF DRAINS | BBENEDON | Approved | IVRS - Inspection :* BELOW GRADE AT TERMINATION OK |
| 12/05/2008 | ELECTRIC - UFER | RMORENO | Approved | IVRS - Inspection :* 3 - 3/4 PVC OUT OF WEST WALL 2 FOR MENS BATHROOM OK 2 FOR WOMENS BATHROOM OK ELECTRIC UFER OK 2 PVC 3/4 OUT OF EAST WALL FOR OUTLETS OK |
| 12/05/2008 | ELECTRIC - UNDERGROUND | RMORENO | Approved | IVRS - Inspection :* |
| 12/11/2008 | STUCCO MESH | JBURGE | Approved | IVRS - Inspection :* EAST WALL -- OK TO STUCCO |
| 12/11/2008 | BUILDING PRE-SLAB | JBURGE | Approved | IVRS - Inspection :* NORTH PORTION -- ALL AREAS EXCEPT PRACTICE GYM #101 OK TO POUR PROGRESS AREAS |
| 12/11/2008 | EXCAVATION/LAYOUT REBAR & ZON | JBURGE | Approved | IVRS - Inspection :* FOOTINGS FOR RESTROOMS #113, 114, RISER ROOM #103 STORAGE ROOMS #111, 112 -- OK TO POUR FOOTINGS |
| 12/12/2008 | PLUMBING - PRE SLAB | BBENEDON | Approved | IVRS - Inspection :* RECALL INSP. FOR FD's AND TRAP PRIMERS |
| 12/15/2008 | PLUMBING - SEWER HCS CONNECT | BBENEDON | Approved | IVRS - Inspection :* DO NOT ALLOW ANY DISCHARGE INTO MAIN SEWER UNTIL YOU HAVE RECEIVED AUTHORIZATION TO DISCHARGE FROM PCDEQ |
| 12/17/2008 | ELECTRIC - INTERMEDIATE | RMORENO | Approved | IVRS - Inspection :* NORTH SIDE OF BUILDING MAINTENANCE WALLS FOR INTERMEDIATE OK |
| 12/30/2008 | REINFORCED MASONRY PRE-GROUT | JBURGE | Approved | IVRS - Inspection :* 1) INTERIOR CMU STAIRWELL WALLS (E & W) AT 4'-8' OK TO GROUT |
| 03/19/2009 | FIRE SPKLR - OH PIPING & HYDRO | LTHOMAS | Approved | |
| 03/25/2009 | BUILDING ABOVE CEILING | JBURGE | Approved | IVRS - Inspection :* STORAGE ROOMS #111 & 112 COMPLETE - OK TO SHEETROCK |
| 03/26/2009 | PLUMBING - ABOVE CEILING | RRICH | Approved | IVRS - Inspection :* |
| 04/01/2009 | SHEET ROCK NAILING | JBURGE | Approved | IVRS - Inspection :* SHEETROCK NAILING IS COMPLETE |
| 05/05/2009 | PLUMBING - INTERMEDIATE | BBENEDON | Approved | IVRS - Inspection :* |
| 06/18/2009 | U VALUE FOR WINDOW | JBURGE | Approved | IVRS - Inspection :* 1) ALL GLASS PANES ARE TEMPERED |
| 06/18/2009 | FRAMING | JBURGE | Approved | IVRS - Inspection :* |
| 06/18/2009 | ROOF NAILING | JBURGE | Approved | IVRS - Inspection :* |
| 06/18/2009 | EXT METAL CLIPS/EXT SHEATHING | JBURGE | Approved | IVRS - Inspection :* |
| 06/24/2009 | FIRE SPKLR - UG PIPING FLUSH | LTHOMAS | Approved | |
| 06/24/2009 | FIRE SPKLR - FINAL | LTHOMAS | Approved | |
| 06/24/2009 | FIRE - ALARM FINAL | LTHOMAS | Approved | |
| 06/24/2009 | FIRE - FINAL | LTHOMAS | Approved | |
| 07/01/2009 | OUTDOOR LIGHTING FINAL | RMORENO | Approved | |
| 07/01/2009 | ELECTRIC - ABOVE CEILING | RMORENO | Approved | |
| 07/01/2009 | ELECTRIC - OUTDOOR LIGHTING | RMORENO | Approved | |
| 07/01/2009 | ELECTRIC - FINAL | RMORENO | Approved | IVRS - Inspection :* 1) STRAPPING, FUSES AND LABELS |
| 07/16/2009 | MECHANICAL - FINAL | JMILITEL | Approved | IVRS - Inspection :* 1) DUCT SMOKE DETECTOR IS OK 2) AIR BALANCE REPORT HAS ISSUES, ENGINEER IS AWARE OF 3) OK FOR FINAL |
| 07/16/2009 | MECHANICAL - ABOVE CEILING | JMILITEL | Approved | IVRS - Inspection :* |
| 07/16/2009 | BUILDING - FINAL | JBURGE | Approved | IVRS - Inspection :* 1) ALL TRADES, FIRE AND APPLICABLE INSPECTION FINALS ARE COMPLETE |
| 07/16/2009 | NPPO - FINAL | PMCLAUGH | Approved | |
| 07/16/2009 | LANDSCAPE - FINAL | PMCLAUGH | Approved | |
| 07/16/2009 | ENGINEERING - FINAL | DROBERTS | Approved | CHECKED THE SITE TO ENSURE THAT ALL OF THE ITEMS HAVE BEEN COMPLETED, ADVISED THE CONTRACTOR TO REMOVE ALL TEMPORARY FENCING MATERIALS FROM THE SITE ONCE HE WAS DONE. |
| 07/16/2009 | RIGHT OF WAY - FINAL | PWHIDDON | Approved | PER EMAIL |
| 07/16/2009 | SIGN - FINAL | JYBARRA | Approved | |
| 07/17/2009 | PERMIT FINALED | LJACKSON | Approved | |
| 07/17/2009 | PLUMBING - FINAL | RRICH | Approved | |
| 07/17/2009 | SITE - SEWER | RRICH | Approved |