Permit: T08CM00039

Parcel: 13329001A


Addresses:

545 N CAMINO SECO

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
07/16/2009 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
04/30/2009 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
FLEX DUCTS NOT INSTALLED PER DETAILS ON PLANS
PROVIDE ODB DAMPERS IN SUPPLY DIFFUSERS
OK FOR CEILING TILES
03/31/2009 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO BACKFILL TRENCH
03/30/2009 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
REMAINDER OF UNDERGROUND PIPING 100 PSI TEST
OK TO INSULATE AND COVER
03/24/2009 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
03/23/2009 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
SUPPLY & EXHAUST IN RESTROOMS AND STORAGE AREAS
OK FOR SHEETROCK
01/29/2009 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
100 PSI TEST ON NEXT SECTION OF UNDERGROUND PIPING
OK TO COVER
01/09/2009 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
100 PSI HYDROSTATIC TEST IS OK ON HYDRONIC PIPING UP TO BACKSTOP. OK TO PROCEED.
11/24/2008 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
100 PSI TEST ON HYDRONIC UNDERGROUND PIPING
RISER SECTION ONLY. OK TO BACKFILL THIS SECTION.