Permit: T08CM00039

Parcel: 13329001A


Addresses:

545 N CAMINO SECO

Inspection Status: Approved

Inspection History: REINFORCED MASONRY PRE-GROUT

Date Description Inspector Results Comments
06/18/2009 REINFORCED MASONRY PRE-GROUT Approved IVRS - Inspection :*
03/02/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
TAPERED EXTERIOR COLUMNS #4 & 5 @ 12'4"
OK TO GROUT
02/27/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
EXTERIOR TAPERED COLUMNS (NORTH) #1, 2, 3 @ 8';
#4, 5 @ 8'8" - OK TO GROUT (DETAIL #115; PAGE S4.1)
02/26/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
NORTHSIDE COLUMNS #1 THRU #5 @ 56" -- OK TO GROUT
02/17/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
STAIRWELL WALLS; MECHANICAL ROOMS
TOPPED OUT
OK TO GROUT - SPECIAL INSPECTED
02/12/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) NORTH WALL AT 20'-32'; STAIRWELL (EAST & WEST) WALLS AT 31'-OK TO GROUT PROGRESS AREAS
02/11/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
WEST MECH/ELEC #202
WALL @ 28'-32' (32'8" CENTER PORTION);
EAST WALL @ 28'-32'; ENSURE PROPER PLACEMENT OF VERTICAL REBARS -- OK TO GROUT PROGRESS AREAS
02/10/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
STAIRWELL WALL (EAST) @ 12'8" AFFE MEZZANINE;
NORTH EXTERIOR WALL (NORTH) FROM STAIRWELL
TO EAST WALL @ 28' OK TO GROUT
02/09/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
EAST MEZZANINE WALL @ 12' AFFE; STAIRWELL @ 12' ABOVE FLOOR FINISHED (2ND FLOOR); NORTH WALL #107 @ 24'-28'
OK TO GROUT PROGRESS AREAS
02/06/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
SOUTH WALL (INFILL) TOPPED OUT @ 35'4" -- OK TO GROUT
02/04/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
ROOM #104, WEST & NORTH WALLS @ 20'-24';
ROOM #101 N.WALL @ 20'-24'; STAIRWELL WALLS @ 8'8" AFFE
MEZZANINE
OK TO GROUT PROGRESS AREAS
ENSURE PROPER PLACEMENT OF REBAR
02/03/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
STAIRWELL (EAST WALL) @ 4'8" ABOVE 2ND FFE;
2ND FLOOR EXTERIOR WALLS; N, E, W @ 16'-20'
OK TO GROUT PROGRESS AREAS
01/30/2009 REINFORCED MASONRY PRE-GROUT Not ready for Inspection IVRS - Inspection :*
01/29/2009 REINFORCED MASONRY PRE-GROUT Partial Approval SOUTH EXTERIOR WALL (INFILL) @ 20'8"-24'8"
OK TO GROUT PROGRESS AREAS
01/28/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
SOUTH EXTERIOR WALL (INFILL) @ 16'8" TO 20'8"
OK TO GROUT
01/27/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
SOUTH EXTERIOR WALL (IN-FILL) @ 12'8"-16'8";
JANITOR ROOM EAST WALL @ 10'4";
STORAGE #111 EAST WALL TOPPED OUT - OK TO GROUT PROGRESS AREAS
01/26/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
SOUTH WALL (INFILL) 8'-12'
CORRECTION OF HEAD JOINT MADE @ 10'
SPECIAL INSPECTION; JANITOR ROOM #110 EAST WALL @ 8'-12' OK TO GROUT
01/23/2009 REINFORCED MASONRY PRE-GROUT Not ready for Inspection IVRS - Inspection :*
WILL RECALL FOR 1/27
01/22/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
SOUTH EXTERIOR WALL (INFILL) @ 4'-8' OK TO GROUT
RESTROOMS - EAST WALL - TOPPED OUT @ 10' OK TO GROUT
01/21/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
EAST RESTROOM WALL @ 8'8";
STORAGE ROOM #112 WEST WALL @ 12'8";
JANITOR ROOM #110 EAST WALL @ 0'-4'
EXTERIOR SOUTH WALL (SE PORTION) @ 0'-4'
OK TO GROUT PROGRESS AREAS
01/16/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
EAST WALL OF RESTROOMS #113-114 @ 56"
WEST VESTIBULE WALL @ 16'4" -- OK TO GROUT
PROGRESS AREAS*

*SPECIAL INSPECTION REPORT #2948JA080 1/14/09
CORRECTIONS COMPLETED 1/16/09
01/15/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
RESTROOM WALLS (EAST) #113 & 114 @ 8'8" - 12'8";
WEST RESTROOM WALL #113;
WEST RISER ROOM WALL #109: 8'8"-12'8" OK TO GROUT
01/13/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
RESTROOM #105 WEST WALL @ 4'8" TO 8'8";
STORAGE ROOM #112 - EAST WALL @ 4'8" - 8'8"
OK TO GROUT
01/12/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
TREATMENT AREA #101 WEST & NORTH WALLS TOPPED OUT
@ 17'4"; NORTH EXTERIOR WALL @ HYDRO ROOM #107 TO STORAGE (EAST) ROOM #112 @ 15'4"; RESTROOM #105 (WEST) @ 4' -- OK TO GROUT PROGRESS AREAS
01/07/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
PERIMETER WALLS @ 8'-12'; INTERIOR WALLS BATHROOMS AND INTERIOR STAIRWELL @ 13'8" -- OK TO GROUT PROGRESS AREAS
01/05/2009 REINFORCED MASONRY PRE-GROUT Not ready for Inspection IVRS - Inspection :*
CONTRACTOR CANCELED -- RAINED OUT
12/30/2008 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) INTERIOR CMU STAIRWELL WALLS (E & W) AT 4'-8' OK TO GROUT
12/29/2008 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) PERIMETER CMU WALLS EXCEPT ON EAT AND WEST ENDS AND INTERIOR CMU WALL AT ROOMS #110, 111, 112, 113, 114, 109, 106 & 115 OK TO GROUT-SPECIAL INSPECTED
12/19/2008 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
4' NORTHERN SECTION
09/03/2008 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
SE CORNER LOBBY CMU WALLS @ 12'-16'
OK TO GROUT PROGRESS AREA
09/02/2008 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
NORTH INTERIOR GYM WALL TOPPED OUT @ 34'4"; LOBBY;
SE WALL @ 8' - 12' OK TO GROUT PROGRESS AREAS
08/29/2008 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
NORTH GYM WALL @ 28'-32'; SOUTH GYM WALL @ 24'
50' TO 70' WEST OF S.E CORNER

EAST GYM WALL PIERS TOPPED OUT @ 29'4"
INTERIOR TROPHY CASE WALLS @ 4' - 8'
OK TO GROUT PROGRESS AREAS
08/27/2008 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
NORTH GYM WALL @ 24'8" - 28'8" (CENTER PORTION)
4 @ VENTS WITH LENTELS ABOVE

WEST GYM WALL PIERS @ 24'8" TO 29'4";
(SOUTH WALL NOT READY) - OK TO GROUT PROGRESS AREAS
08/25/2008 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
SOUTH GYM WALL (CONSTRUCTION ACCESS) WEST
APPROX. 32' @ 28'8" -- OK TO GROUT PROGRESS AREA
08/22/2008 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
NORTH INTERIOR GYM WALL - APPROX. 80' FROM
NW CORNER @ 20'8" TO 24'8"

* WEST GYM WALL @ 20'8" TO 24'8"
* SOUTH GYM WALL APPROX. 45' FROM SW CORNER @ 20'8" - 24'8" -- OK TO GROUT PROGRESS AREAS
08/20/2008 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
N.E CORNER OF NORTH INTERIOR WALL &
EAST GYM WALL @ 20'8" OK TO GROUT
08/18/2008 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
NE CORNER GYM AREA @ 17'6";
PERIMETER GYM WALLS @ 20'8" EXCEPT NW CORNER (GROUTED @ 17'6") OK TO GROUT PROGRESS AREAS
08/13/2008 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
WEST GYM WALL @ 16'8"; NORTH INTERIOR WALL @ 16'8";
SW WALL OF ROOM #102 @ 16'8" -- OK TO GROUT
08/12/2008 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
NORTH INTERIOR WALL @ 12'8" (EXCEPT NE CORNER)
SOUTH WALL (GYM) WEST TO EAST FROM SW CORNER
APPROX. 45' @ 16'8" -- OK TO GROUT
NW STORAGE ROOM #102 - SW WALL @ 8'8" -- OK TO GROUT
08/11/2008 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
SOUTH GYM WALL @ SE CORNER APPROX. 20' @ 16'8"
EAST GYM WALL NE APPROX. 16' @ 16'8"
OK TO GROUT PROGRESS AREAS
08/08/2008 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
WEST WALL (ALL); S. GYM WALL 0-20'
E OF SW CORNER; 27-50' - E - OF SW CORNER;
N.WALL @ 0-12' E OF NW CORNER ALL HEIGHTS @ 8'7" TO 12'7"

E.WALL 3' SOUTH OF NE CORNER TO 4' NORTH OF SE CORNER
@ 12'7" TO 16'7"
GROUTED & SPECIAL INSPECTED
08/06/2008 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) EAST WALL AT 12'; NW INTERIOR WALLS AT FIRST TWO; LINTELS AT 8'; SW. EXTERIOR WALL AT ROOM #101 AT 4' SE LOBBY EXTERIOR WALL AT 4'-OK TO GROUT PROGRESS AREAS
08/04/2008 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
EXTERIOR CMU WALLS - WEST, EAST, SOUTH @ 4'-8'
OK TO GROUT PROGRESS AREAS
07/31/2008 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
NORTH INTERIOR WALL @ SW CORNER OF ROOM #102 TO ENTRY DOOR #100G @ 0'-4'
OK TO GROUT
07/30/2008 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
EAST, WEST & SOUTH WALLS (EXTERIOR) @ 0' - 4'
OK TO GROUT PROGRESS AREAS