Permit Details

Status:
C of o
Type:
COMMERCIAL ALTERATION
Address:
2501 E ELM ST
Address NEW:
2501 E ELM ST
Apply Date:
12/05/2007
Applicant:
METRO PERMIT EXPRESS, INC *C
Description:
TI:HEALTH CENTER
Architects:
  • MASCIA, FRANK
Contractors:
  • KNOTHOLE CREATIONS L L C

Permit Reviews

Permit Number - T07CM04543
Permit Status: C of o
Permit Description: TI:HEALTH CENTER
Start Date Submittal Complete Date Status  
02/04/2008 POST 3RD PARTY REVIEW 02/13/2008 COMPLETED Review Details
12/05/2007 PLANS OK TO SUBMIT - 3RD PARTY 12/12/2007 COMPLETED Review Details
12/12/2007 3RD PARTY REVIEW-COMMERCIAL TI 02/04/2008 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T07CM04543
Permit Status: C of o
Permit Description: TI:HEALTH CENTER
Total Outstanding Activity Conditions - 1
Date Name
12/05/2007 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: C of o
Permit Number: T07CM04543
Permit Description: TI:HEALTH CENTER
Total Completed Inspections - 25
Date Description Inspector Results Comments
02/22/2008 PLUMBING - PRE SLAB BBENEDON Approved IVRS - Inspection :*
YOU WILL NEED TO REMOVE AND PLUG ABANDON PIPE PENTRATIONS THRU SLAB AND ROOF
03/21/2008 FRAMING AQUIROZ Approved IVRS - Inspection :*
03/25/2008 MECHANICAL - INTERMEDIATE JMILITEL Approved IVRS - Inspection :*
- FLEX DUCTS & HANGER STRAPS NOT INSTALLED PER PLAN
SEE DETAIL M2.0
- SOME DIFFUSERS MISSING OBD FOR BALANCING
- REPLACE DAMAGED SUPPLY DUCT
- OK TO SHEETROCK SOFFITS
- SEAL SPOT WELDS & SEAMS ON NEW DUCT ON ROOF
- SUPPORT GAS LINES
- REMOVE GAS FLEX FROM SW UNIT
- PROVIDE CONDENSATE DRAINS AS NEEDED
- RESUPPORT CONDENSATE DRAINS
- PROVIDE TRAPS AS NEEDED
- PROVIDE FRESH AIR INTAKES AS NEEDED
- GAS FLEX CANNOT PENETRATE THE CABINET OF A FURNACE
- RESUPPORT ELEC. CONDUITS
- PROVIDE SERVICE RECEPTACLES ON ROOF AS
REQUIRED BY NEC
03/28/2008 SHEET ROCK NAILING JBURGE Approved IVRS - Inspection :*
OK TO TAPE THROUGHOUT
04/02/2008 PLUMBING - INTERMEDIATE RMYERS Approved IVRS - Inspection :*
04/02/2008 PLUMBING - ABOVE CEILING RMYERS Approved IVRS - Inspection :*
04/16/2008 BUILDING ABOVE CEILING JBURGE Approved IVRS - Inspection :*
OK TO SET TILES
04/23/2008 MECHANICAL - ABOVE CEILING MRAMBER Approved IVRS - Inspection :*
04/25/2008 MECHANICAL - HOODS JMILITEL Approved IVRS - Inspection :*
04/29/2008 ELECTRIC - FINAL CCLEMENS Approved IVRS - Inspection :*
04/29/2008 ELECTRIC - TEMPORARY SERVICE CCLEMENS Approved IVRS - Inspection :*
04/29/2008 ELECTRIC - CABLE DROP CCLEMENS Approved IVRS - Inspection :*
04/29/2008 ELECTRIC - ABOVE CEILING CCLEMENS Approved IVRS - Inspection :*
04/29/2008 ELECTRIC - INTERMEDIATE CCLEMENS Approved IVRS - Inspection :*
05/01/2008 BUILDING - FINAL JBURGE Approved IVRS - Inspection :*
PENDING FIRE FINAL -- ALL TRADES ARE COMPLETE
05/01/2008 FIRE SPKLR - FINAL CSCHULTZ Approved
05/01/2008 FIRE - FINAL CSCHULTZ Approved
05/01/2008 PLUMBING - FINAL RMYERS Approved IVRS - Inspection :*
05/01/2008 MECHANICAL - FINAL MRAMBER Approved IVRS - Inspection :*
05/02/2008 RIGHT OF WAY - FINAL MOTERO Approved PER EMAIL
05/02/2008 NPPO - FINAL JLINVILL Approved
05/02/2008 LANDSCAPE - FINAL JLINVILL Approved
05/02/2008 ENGINEERING - FINAL NKALAHAR Approved NO SITE WORK PER PLAN
REMINDED CONTRACTOR TO FINISH ALL CLEAN UP INCLUDING PAINT CANS AT N SIDE OF BUILDING
05/02/2008 SIGN - FINAL JYBARRA Approved IVRS - Inspection :*
05/05/2008 PERMIT FINALED BFLORES Approved