Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T07CM04543
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/29/2008 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 04/16/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 04/02/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SECURE ALL FIXTURES TO GRID 2. SUPPORT ALL EQUIPMENT OFF GRID & TO STRUCTURE 3. WIRE NUTS TO BE USED AS LISTED 4. SHEETMETAL SCREWS NOT ALLOWED FOR GROUND CONNECTION 5. CLOSE OFF UNUSED OPENINGS 6. OCCUPANCY SENSOR WIRING NOT COMPLETE 7. EMERGENCY LIGHTING NOT COMPLETE 8. FINISH ALL WIRING IN CEILING |