Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T07CM03195
Permit Details
Apply Date:
07/31/2007
Applicant:
JACA DESIGN LLC
Description:
TI:MARKET
Contractors:
- GAD CONTRACTING L L C
Permit Reviews
Permit Number - T07CM03195
Permit Status: C of o
Permit Description: TI:MARKET
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
06/19/2008 | 3RD PARTY REVIEW-REVISION/OTHER-2ND | 06/20/2008 | COMPLETED |
07/31/2007 | PLANS OK TO SUBMIT - 3RD PARTY | 08/14/2007 | COMPLETED |
08/01/2008 | REVISION - - 3RD | 08/01/2008 | COMPLETED |
08/14/2007 | 3RD PARTY REVIEW-COMMERCIAL TI | 10/23/2007 | COMPLETED |
10/23/2007 | POST 3RD PARTY REVIEW | 10/24/2007 | COMPLETED |
12/28/2007 | 3RD PARTY REVIEW-REVISION/OTHER | 12/31/2007 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T07CM03195
Permit Status: C of o
Permit Description: TI:MARKET
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
07/31/2007 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: C of o
Permit Number: T07CM03195
Permit Description: TI:MARKET
Total Completed Inspections - 29
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/07/2007 | PLUMBING - ROUGH, SOIL | RRICH | Approved | IVRS - Inspection : See detailed listing on site.| 999* 1. SEE CHAPTER 10 SECTION 1014.2 FOR CORRECT INSTALLATION OF HYDROMECHANICAL INTERCEPTORS 2. YOUR ISOMETRIC PLAN SHOWS FIXTURES WITH NO VENTS, 2006 UPC REQUIREMENTS ARE FOR ALL TRAPS TO BE VENTED 3. CHANGES FROM APPROVED REQUIRE MINIMUM REDLINES ON SITE AT TIME OF INSPECTION. |
12/12/2007 | MECHANICAL - HOODS | JMILITEL | Approved | IVRS - Inspection :* OK TO FIRE WRAP GREASE DUCT & INSTALL |
12/28/2007 | FRAMING | GDABBS | Approved | IVRS - Inspection : See detailed listing on site.| 999* NEED COMPLETE SET OF BOUND APPROVED PLANS |
01/15/2008 | PLUMBING - PRE SLAB | RRICH | Approved | IVRS - Inspection :* |
01/23/2008 | SHEET ROCK NAILING | GDABBS | Approved | IVRS - Inspection :* |
01/23/2008 | PLUMBING - INTERMEDIATE | RRICH | Approved | IVRS - Inspection :* |
06/16/2008 | PLUMBING - GAS PRESSURE TEST | RMYERS | Approved | IVRS - Inspection :* 1. IT APPEARS THAT THERE ARE MULTIPLE UNITS/SUITES AT 4211 E 22ND ST ADDRESSING IS CRITICAL AND ADDRESS AND SUITE NUMBER ARE TO BE POSTED PRIOR TO THIS INSPECTION 2. ALL CHANGES TO THE PLAN TO BE ACCOMPANIED BY REDLINES, OR REVISED APPROVED PLAN 3. ABS TO BE SUPPORTED AT EACH CHANGE OF DIRECTION OR ELEVATION AND AT THE END OF BRANCHES THEN NO MORETHAN 4' BETWEEN HANGERS 4. CONTINUATION OF GAS PIPING TO STEAM TABLE OK TEST ON ENTIRE SYSTEM OK |
06/16/2008 | PLUMBING - ABOVE CEILING | RMYERS | Approved | IVRS - Inspection :* |
07/10/2008 | MECHANICAL - ABOVE CEILING | JMILITEL | Approved | IVRS - Inspection :* |
07/16/2008 | ELECTRIC - FINAL | RJIROUDE | Approved | IVRS - Inspection :* |
07/16/2008 | ELECTRIC - ABOVE CEILING | RJIROUDE | Approved | IVRS - Inspection :* |
07/16/2008 | ELECTRIC - INTERMEDIATE | RJIROUDE | Approved | IVRS - Inspection :* |
07/21/2008 | PLUMBING - FINAL | RRICH | Approved | IVRS - Inspection :* RECEIVED BACTERIA REPORT FOR POTABLE WATER RECEIVED (2) IN HOUSE BACKFLOW CERTIFICATIONS POST A BOND AND GET MECHANICAL INSPECTOR OK FOR GAS CLEARANCE CARD |
07/21/2008 | PLUMBING - GAS PRESS TEST FNL | RRICH | Approved | IVRS - Inspection :* |
08/01/2008 | FIRE - KITCHEN EXH HOOD FINAL | LLAKEY | Approved | |
08/06/2008 | FIRE - FINAL | LLAKEY | Approved | |
08/07/2008 | MECHANICAL - FINAL | JMILITEL | Approved | IVRS - Inspection :* OK FOR FINAL |
08/07/2008 | MECHANICAL - HOOD SYSTEMS | JMILITEL | Approved | IVRS - Inspection :* |
08/07/2008 | MECHANICAL - INTERMEDIATE | JMILITEL | Approved | IVRS - Inspection :* |
08/08/2008 | BUILDING - FINAL | GDABBS | Approved | IVRS - Inspection :* |
08/08/2008 | BUILDING ABOVE CEILING | GDABBS | Approved | IVRS - Inspection :* |
08/12/2008 | RIGHT OF WAY - FINAL | MCASTRO | Approved | PER EMAIL |
08/12/2008 | NPPO - FINAL | ACONNOR | Approved | |
08/12/2008 | LANDSCAPE - FINAL | ACONNOR | Approved | |
08/12/2008 | ENGINEERING - FINAL | NKALAHAR | Approved | NO SITE WORK PER PLAN |
08/13/2008 | SIGN - FINAL | JYBARRA | Approved | |
08/18/2008 | HEALTH DEPT - FINAL 724-7908 | LANDERSON | Approved | |
08/19/2008 | PERMIT FINALED | LJACKSON | Approved | |
08/19/2008 | FIRE SPKLR - FINAL | LLAKEY | Approved |