Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/16/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/10/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED PROPER WORKING CLEARANCE ON DISCONNECT FOR KWIK-THAW PROOFER 2. SEAL OPENING BELL BOX IN WALK IN COOLER 3. HAVE RECEPT WITH NO POWER 4. PROVIDE DISCONNECTING MEANS FAN COIL UNITS WALK IN COOLERS 5. SEAL RACEWAYS INTO WALK IN COOLERS 6. STRAP EMT ON ROOF WITHIN 3' OF CONNECTION 7. NEED GFI SERVICE RECEPTACLES WITHIN 25' OF A/C AND REFRIGERATION EQUIP. 8. PROPERLY GROUND AC DISCONNECT 9. PROPERLY SECURE AC DISCONNECT 10. EXISTING ROOFTOP GFI RECEPTACLES NOT TRIPPING WHEN TESTED |