Inspection Status: Approved
Inspection History: MECHANICAL - HOODS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/01/2008 | MECHANICAL - HOODS | Approved | IVRS - Inspection :* CHECKED FIRE WRAP |
|
| 04/28/2008 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* CHECKED WELDS ON GREASE DUCT OK TO FIRE WRAP |
|
| 04/21/2008 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* CHECKED WELDS ON GREASE DUCTS OK TO FIRE WRAP 1ST PIECE OF DUCT AND INSTALL NEED TO CHECK WELDED JOINT |
|
| 03/10/2008 | MECHANICAL - HOODS | Not ready for Inspection | IVRS - Inspection :* 2006 IMC REQUIRES 2 LAYERS OF FIRE WRAP & A HEAT SENSOR IN THE BOTTOM OF THE DUCT. REDESIGN GREASE DUCT TO FIT BETWEEN TRUSSES DESIGNED BY ENGINEER AND HAVE ENGINEER PROVIDE AN ELEC. DETAIL ON PLANS FOR HEAT SENSOR WIRING. |
|
| 02/14/2008 | MECHANICAL - HOODS | Denied | IVRS - Inspection : See detailed listing on site.| 999* DOORS LOCKED. NO ACCESS. |
|
| 12/12/2007 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* OK TO FIRE WRAP GREASE DUCT & INSTALL |