Permit: T07CM03195

Parcel: 12618217A


Addresses:

4211 E 22ND ST


Inspection Status: Approved

Inspection History: MECHANICAL - HOODS

Permit Number - T07CM03195

Inspection Description - MECHANICAL - HOODS

Inspection Status - Approved

Date Description Inspector Results Comments
05/01/2008 MECHANICAL - HOODS Approved IVRS - Inspection :*
CHECKED FIRE WRAP
04/28/2008 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
CHECKED WELDS ON GREASE DUCT
OK TO FIRE WRAP
04/21/2008 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
CHECKED WELDS ON GREASE DUCTS
OK TO FIRE WRAP 1ST PIECE OF DUCT AND INSTALL
NEED TO CHECK WELDED JOINT
03/10/2008 MECHANICAL - HOODS Not ready for Inspection IVRS - Inspection :*
2006 IMC REQUIRES 2 LAYERS OF FIRE WRAP & A HEAT SENSOR IN THE BOTTOM OF THE DUCT. REDESIGN GREASE DUCT TO FIT BETWEEN TRUSSES DESIGNED BY ENGINEER AND HAVE ENGINEER PROVIDE AN ELEC. DETAIL ON PLANS FOR HEAT SENSOR WIRING.
02/14/2008 MECHANICAL - HOODS Denied IVRS - Inspection :
See detailed listing on site.| 999*
DOORS LOCKED. NO ACCESS.
12/12/2007 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
OK TO FIRE WRAP GREASE DUCT & INSTALL