Permit: T07CM03195

Parcel: 12618217A


Addresses:

4211 E 22ND ST


Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Permit Number - T07CM03195

Inspection Description - PLUMBING - GAS PRESSURE TEST

Inspection Status - Approved

Date Description Inspector Results Comments
06/16/2008 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
1. IT APPEARS THAT THERE ARE MULTIPLE UNITS/SUITES
AT 4211 E 22ND ST ADDRESSING IS CRITICAL AND ADDRESS AND SUITE NUMBER ARE TO BE POSTED PRIOR TO THIS INSPECTION
2. ALL CHANGES TO THE PLAN TO BE ACCOMPANIED BY REDLINES, OR REVISED APPROVED PLAN
3. ABS TO BE SUPPORTED AT EACH CHANGE OF DIRECTION OR ELEVATION AND AT THE END OF BRANCHES THEN NO MORETHAN 4' BETWEEN HANGERS
4. CONTINUATION OF GAS PIPING TO STEAM TABLE OK
TEST ON ENTIRE SYSTEM OK
02/14/2008 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
FROM METER THRU TO ROOF TOP UNITS VALVES, TO WATER HEATER, CAP AT DOUBLE OVEN AT 10' AFF, THRU ANSUL VALVE TO HOOD VALVES AND CAP FOR CONTINUATION TO STEAM TABLE.
02/08/2008 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
FAILURE TO COMPLETE WORK AND PROVIDE ACCESS WILL RESULT IN A REINSPECTION FEE.
02/06/2008 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
CONTRACTOR CANCELED
02/05/2008 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. ACTUAL CITY APPROVED GAS ISOMETRIC DRAWING IS REQUIRED FOR THIS INSTALLATION
2. AGA OR CSA APPROVED GAS VALVE REQUIRED AT ENTRY INTO BLD. AND UPSTREAM OF ANSUL VALVE.
3. ALL PIPING TO BE SUPPORTED AT CORRECT INTERVALS
4. PROVIDE ACCESS TO ROOF TOP