Permit: T07CM03195

Parcel: 12618217A


Addresses:

4211 E 22ND ST


Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T07CM03195

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
01/23/2008 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
01/22/2008 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
- WATER TEST TO INTERCEPTOR OK
- SHALL TEST TO TIE IN INTO SEWER
- PROVIDE GREEN TRACER WIRE FOR UNDERGROUND
NON-METALLIC PIPING
01/15/2008 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
WATER TEST DWV THRU ROOF OK EXCEPT P-5 IN BAKERY REQUIRES VENT FOR TRAP.
P-3 PREP SINKS ARE TO BE INDIRECTLY DRAINED TO APPROVED RECEPTOR IN KITCHEN AREA. SHALL SEE CONTINUATION OF 4" FROM INTERIOR TO
INTERCEPTOR & BUILDING SEWER
01/14/2008 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
CONTRACTOR CANCELLED
11/07/2007 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SEE CHAPTER 10 SECTION 1014.2 FOR CORRECT INSTALLATION OF HYDROMECHANICAL INTERCEPTORS
2. YOUR ISOMETRIC PLAN SHOWS FIXTURES WITH NO VENTS, 2006 UPC REQUIREMENTS ARE FOR ALL TRAPS TO BE VENTED
3. CHANGES FROM APPROVED REQUIRE MINIMUM REDLINES ON SITE AT TIME OF INSPECTION.