Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T06CM01979
Permit Details
Apply Date:
04/06/2006
Applicant:
VENEZIANO, PHILIP JOHN
Description:
CONVENIENCE STORE:REBUILD
Architects:
- VENEZIANO, PHILIP JOHN
Contractors:
- FARWEST DEVELOPMENT AND CONSTRUCTION OF THE SOUT
Permit Reviews
Permit Number - T06CM01979
Permit Status: C of o
Permit Description: CONVENIENCE STORE:REBUILD
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 04/06/2006 | PLANS OK TO SUBMIT - SITE | 04/06/2006 | COMPLETED |
| 04/06/2006 | 3RD PARTY REVIEW-COMMERCIAL TI | 04/07/2006 | COMPLETED |
| 04/07/2006 | 3RD PARTY REVIEW-COMMERCIAL | 06/16/2006 | COMPLETED |
| 04/10/2006 | SITE | 06/07/2006 | COMPLETED |
| 05/09/2007 | 3RD PARTY REVIEW-REVISION/OTHER | 05/09/2007 | COMPLETED |
| 05/09/2007 | POST 3RD PARTY REVIEW | 06/01/2007 | COMPLETED |
| 06/01/2007 | 3RD PARTY REVIEW-REVISION/OTHER | 06/01/2007 | COMPLETED |
| 06/07/2006 | RESUBMITTAL - SITE | 06/30/2006 | COMPLETED |
| 06/16/2006 | POST 3RD PARTY REVIEW | 06/30/2006 | COMPLETED |
| 06/30/2006 | RESUBMITTAL | 08/30/2006 | COMPLETED |
| 07/11/2007 | 3RD PARTY REVIEW-REVISION/OTHER | 08/21/2007 | COMPLETED |
| 07/13/2006 | OTHER | 07/13/2006 | COMPLETED |
| 09/13/2007 | 3RD PARTY REVIEW-REVISION/OTHER | 09/13/2007 | COMPLETED |
| 12/15/2006 | 3RD PARTY REVIEW-REVISION/OTHER | 12/15/2006 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T06CM01979
Permit Status: C of o
Permit Description: CONVENIENCE STORE:REBUILD
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 04/06/2006 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: C of o
Permit Number: T06CM01979
Permit Description: CONVENIENCE STORE:REBUILD
Total Completed Inspections - 46
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/14/2006 | EXCAVATION/LAYOUT REBAR & ZON | LHANLY | Approved | IVRS - Inspection :* 2 EACH CAISSONS @ NEW GAS ISLAND FOR CANOPY |
| 11/06/2006 | ELECTRIC - UNDERGROUND | CCLEMENS | Approved | IVRS - Inspection :* 1. PLANS NEED TO BE REVISED TO SHOW ALL UNDERGROUND WIRING TO NEW DISPENSERS AND TEMPORARY STORE LOCATION -- OK TO COVER TRENCH TO NEW DISPENSERS BASED ON APPROVED PLANS (RIGID NON-METALLIC RACEWAYS CHANGED TO ROB ROY/RIGID METAL OVER 2' FROM DISPENSERS WITH 24" COVER. |
| 12/06/2006 | BUILDING PRE-SLAB | AQUIROZ | Approved | IVRS - Inspection :* INCOMPLETE |
| 12/12/2006 | ELECTRIC - INTERMEDIATE | CCLEMENS | Approved | IVRS - Inspection :* OK TO POUR SOUTHSIDE DISPERSER SEAL OFF'S (4) AND @ GUTTER (9) SEAL OFF'S |
| 12/19/2006 | ELECTRIC - FINAL | CCLEMENS | Approved | IVRS - Inspection :* OK CONTINUED USE OF FOUR NEW DISPENSERS MAKE SURE SEAL OFF'S REMAIN ACCEPTABLE. |
| 03/21/2007 | SITE - SEWER | BBENEDON | Approved | IVRS - Inspection :* |
| 03/21/2007 | SITE - SEWER | BBENEDON | Approved | IVRS - Inspection :* |
| 03/21/2007 | PLUMBING - SEWER HCS CONNECT | BBENEDON | Approved | IVRS - Inspection :* |
| 04/02/2007 | ELECTRIC - UFER | CCLEMENS | Approved | IVRS - Inspection :* OK #4 TO UFER - STORE BUILDING OK #4 TO UFER - ELECTRICAL ROOM NOTE: A 3/0 CU CONDUCTOR WAS ALSO RAN FROM STORE FOOTING, THROUGH ELECTRICAL ROOM FOOTING, AND BACK TO SERVICE AREA FOR REASONS THAT ARE UNCLEAR AT THIS TIME |
| 04/02/2007 | PLUMBING - PRE SLAB | RMYERS | Approved | IVRS - Inspection :* OK FOR CONCRETE SUBJECT TO REVISED APPROVED PLAN. |
| 04/17/2007 | REINFORCED MASONRY PRE-GROUT | AQUIROZ | Approved | IVRS - Inspection :* |
| 05/23/2007 | PLUMBING - ROOF DRAINS | RMYERS | Approved | IVRS - Inspection :* WATER TEST OK OK TO COVER |
| 06/01/2007 | PLUMBING - ROUGH, SOIL | RMYERS | Approved | IVRS - Inspection :* |
| 06/04/2007 | ROOF NAILING | AQUIROZ | Approved | IVRS - Inspection :* |
| 06/11/2007 | EXT METAL CLIPS/EXT SHEATHING | AQUIROZ | Approved | IVRS - Inspection :* |
| 06/12/2007 | MECHANICAL - INTERMEDIATE | JMILITEL | Approved | IVRS - Inspection :* OK FOR SHEETROCK CONDENSATE DRAINS OK TO INSULATE PROVIDE R-5 DUCT WRAP & LINER FOR ALL DUCT IN UNCONDITIONAL SPACES AS PER PLANS & CODE |
| 06/20/2007 | PLUMBING - GAS PRESSURE TEST | RMYERS | Approved | IVRS - Inspection :* |
| 06/20/2007 | PLUMBING - INTERMEDIATE | RMYERS | Approved | IVRS - Inspection :* |
| 06/26/2007 | SHEET ROCK NAILING | AQUIROZ | Approved | IVRS - Inspection :* |
| 06/26/2007 | FRAMING | AQUIROZ | Approved | IVRS - Inspection :* |
| 06/29/2007 | STUCCO MESH | AQUIROZ | Approved | IVRS - Inspection :* |
| 07/19/2007 | BUILDING ABOVE CEILING | AQUIROZ | Approved | IVRS - Inspection :* |
| 07/20/2007 | PLUMBING - ABOVE CEILING | RMYERS | Approved | IVRS - Inspection :* |
| 07/27/2007 | STEM WALL/RETAINING WALL | AQUIROZ | Approved | IVRS - Inspection :* |
| 07/31/2007 | MECHANICAL - HOODS | AQUIROZ | Approved | IVRS - Inspection :* |
| 08/07/2007 | MECHANICAL - ABOVE CEILING | JMILITEL | Approved | IVRS - Inspection :* OK FOR CEILING TILES |
| 08/15/2007 | RIGHT OF WAY - FINAL | MOTERO | Approved | PER EMAIL |
| 08/15/2007 | MECHANICAL - HOOD SYSTEMS | JMILITEL | Approved | IVRS - Inspection :* |
| 08/15/2007 | U VALUE FOR WINDOW | AQUIROZ | Approved | IVRS - Inspection :* |
| 08/15/2007 | ELECTRIC - ABOVE CEILING | CCLEMENS | Approved | IVRS - Inspection :* |
| 08/15/2007 | NPPO - FINAL | ACONNOR | Approved | |
| 08/15/2007 | SIGN - FINAL | JYBARRA | Approved | NO SIGNS INSTALLED ON THIS BLDG TO DATE |
| 08/17/2007 | OUTDOOR LIGHTING FINAL | CCLEMENS | Approved | IVRS - Inspection :* |
| 08/17/2007 | ELECTRIC - OUTDOOR LIGHTING | CCLEMENS | Approved | IVRS - Inspection :* |
| 08/17/2007 | FIRE SPKLR - FINAL | LTHOMAS | Approved | |
| 08/20/2007 | MECHANICAL - FINAL | JMILITEL | Approved | IVRS - Inspection :* 1) CORRECTIONS HAVE BEEN MADE 2) OK FOR FINAL |
| 08/20/2007 | LANDSCAPE - FINAL | ACONNOR | Approved | |
| 08/21/2007 | HEALTH DEPT - FINAL 724-7908 | MRAMIREZ | Approved | |
| 09/13/2007 | PLUMBING - GAS PRESS TEST FNL | RMYERS | Approved | |
| 09/13/2007 | PLUMBING - YARD WTR LINE/TEST | RMYERS | Approved | |
| 09/13/2007 | FIRE - FINAL | LTHOMAS | Approved | |
| 09/17/2007 | ENGINEERING - FINAL | MRUSSO | Approved | |
| 09/19/2007 | ELECTRIC - TEMP POWER FOR TEST | CCLEMENS | Approved | |
| 09/20/2007 | BUILDING - FINAL | RMYERS | Approved | IVRS - Inspection :* |
| 09/20/2007 | PLUMBING - FINAL | RMYERS | Approved | IVRS - Inspection :* |
| 09/21/2007 | PERMIT FINALED | CCLEMENS | Approved |