Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM01979
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/19/2007 | ELECTRIC - INTERMEDIATE | Approved | ||
08/10/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) CALL WHEN COMPLETE |
|
07/10/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* INTERIOR PANEL WALL @ STORE |
|
06/26/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* PANEL WALL NOT READY I WILL LOOK ABOVE WALKIN, ETC ON FINAL PROVIDE ACCESS HOLE TO THIS AREA |
|
06/12/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK INTERIOR WALL COVER - EXCEPT PANEL WALL AREA |
|
06/08/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | 1. SUPPORT M/C CABLE UPON EXITING WALL 2. SUPPORT M/C CABLE WITHIN 12" OF EXHAUST FAN, BOXES 3. SUPPORT CONDUIT WITHIN 3' OF BOXES 4. PROTECT M/C CABLE IN CHANNELS 330.17 5. SUPPORT M/C CABLE 6' INTERVALS ACROSS STUDS 6. VDV CABLING TO BE SUPPORTED IN WALLS 725.6 |
|
01/11/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TEMPORARY SALES TRAILER FEEDER/PANEL |
|
12/12/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO POUR SOUTHSIDE DISPERSER SEAL OFF'S (4) AND @ GUTTER (9) SEAL OFF'S |