Permit: T06CM01979

Parcel: 10510089H


Addresses:

4370 N 1ST AV 01


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T06CM01979

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
09/19/2007 ELECTRIC - INTERMEDIATE Approved
08/10/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) CALL WHEN COMPLETE
07/10/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
INTERIOR PANEL WALL @ STORE
06/26/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
PANEL WALL NOT READY
I WILL LOOK ABOVE WALKIN, ETC ON FINAL
PROVIDE ACCESS HOLE TO THIS AREA
06/12/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK INTERIOR WALL COVER - EXCEPT PANEL WALL AREA
06/08/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection 1. SUPPORT M/C CABLE UPON EXITING WALL
2. SUPPORT M/C CABLE WITHIN 12" OF EXHAUST FAN, BOXES
3. SUPPORT CONDUIT WITHIN 3' OF BOXES
4. PROTECT M/C CABLE IN CHANNELS 330.17
5. SUPPORT M/C CABLE 6' INTERVALS ACROSS STUDS
6. VDV CABLING TO BE SUPPORTED IN WALLS 725.6
01/11/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TEMPORARY SALES TRAILER FEEDER/PANEL
12/12/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO POUR SOUTHSIDE DISPERSER SEAL OFF'S (4) AND @ GUTTER (9) SEAL OFF'S