Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T06CM01979
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/20/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
09/19/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) FINISH INSULATING PIPES AT WATE HEATER. SUPPORT RECIRCULATION PUMP 2) PAN DRAIN TO BE GRAVITY DRAIN 3) PVC PIPE REQUIRES PRIMER 4) EXTERIOR MECHANICAL ROOM LOCKED 5) CONTINUED NOT READYS WILL RESULT IN A REINSPECTION FEE |
|
09/13/2007 | PLUMBING - FINAL | Not ready for Inspection | 1. ALL SINKS REQUIRE CLEANOUTS 2. ALL CLEANOUTS REQUIRE PLUGS 3. HEAT TRAPS AND INSULATION AT WATER HEATER |
|
08/17/2007 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* REMOVE CONCRETE AT 1 1/2" SERVICE TEMPERING VALVE INSTALLED AT WH FOR PUBLIC LAVS |
|
08/15/2007 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* - CALL FOR AND HAVE APPROVED 3040 & 3052 - PROVIDE CLEARANCE TO SERVICE BACKFLOW ASSEMBLIES IDENTIFY AND CERTIFY 5' MAX - PROPERLY PRIME AND GLUE ALL INDIRECT DRAINS - INSTALL TEMPERING VALVES AT PUBLIC LAVS - COMPLETE ALL WORK FOR FINAL |