Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T06CM01979

Parcel: 10510089H


Addresses:

4370 N 1ST AV 01


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM01979

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/19/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/14/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. WHAT ARE EXISTING CIRCUITS & PUMPS - 408.4 REQUIRES LABELING OF CIRCUITS
2. VERIFY DERATING OF CONDUCTORS IN NEW FLEX CONDUIT B/PANEL ALSO, SUPPORT AS PER CODE
3. MAINTAIN WORKING CLEARANCE UNIT BATHROOM AC IN CORNER 110.26
09/13/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
SPACE OCCUPIED AND IN USE WITHOUT APPROVAL
08/17/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
08/16/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
NEED DISCONNECTS FOR WALK IN FAN COILS
08/15/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
INSPECTION FOR ROOFTOP
1. OVERCURRENT PROTECTION TO BE PER DATA PLATE
2. STRAPS FOR FLEX TO BE SECURE/NEED ANCHORS
3. DISCONNECTS TO HAVE PROPER FRONT - WORKING CLEARANCE
4. ROOFTOP EQUIPMENT TO BE PROPERLY IDENTIFIED ON PANEL SCHEDULE

INSPECTION FOR STORE INTERIOR
1. PERMANENT PANEL DIRECTORIES NEEDED - NEC 408.4
2. PLAN SHOWS DISCONNECTS FOR FCI'S
3. NEED 40 AMP CKT TO WH1
4. ALL KITCHEN 120V 20 AMP RECEPTACLES NEED GFI PROTECTION.

SPACE IS NOT TO BE OCCUPIED BEFORE APPROVAL
08/10/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
12/19/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
OK CONTINUED USE OF FOUR NEW DISPENSERS
MAKE SURE SEAL OFF'S REMAIN ACCEPTABLE.
12/15/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
INSPECTION FOR THE USE OF FOUR NEW FUEL DISPENSER ON SOUTHSIDE ONLY.

PROVIDE COMPLIANCE LETTER
1. CHANGE PERMIT TO REFLECT CORRECT ADDRESS
(4390 N 1ST AV NOT 4370)
2. INSTALL REQUIRED SEAL OFF'S NEXT TO PUMP 3 AS REQUIRED BY NEC 514.9
OK TO PACK AND POUR. CALL FOR AN INSPECTION FOR THESE FITTINGS NO LATER THAN 12/19/06. MAKE SURE THESE FITTINGS REMAIN ACCESSIBLE NEC 314.29
3. EMERGENCY SHUT OFF TO BE ISOLATED FROM OTHER POWER AND LIGHT CONDUCTORS UNLESS TEMPORARY
OK TO USE PUMPS AFTER CORRECTIONS.
12/14/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
HAVE ADDRESS CORRECTED TO PROPER ADDRESS ON PERMIT
12/13/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
NEED REVISED PLAN TO BE APPROVED BY ORIGINAL PLAN REVIEWER.