Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM01979
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/19/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
09/14/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. WHAT ARE EXISTING CIRCUITS & PUMPS - 408.4 REQUIRES LABELING OF CIRCUITS 2. VERIFY DERATING OF CONDUCTORS IN NEW FLEX CONDUIT B/PANEL ALSO, SUPPORT AS PER CODE 3. MAINTAIN WORKING CLEARANCE UNIT BATHROOM AC IN CORNER 110.26 |
|
09/13/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* SPACE OCCUPIED AND IN USE WITHOUT APPROVAL |
|
08/17/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
08/16/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* NEED DISCONNECTS FOR WALK IN FAN COILS |
|
08/15/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* INSPECTION FOR ROOFTOP 1. OVERCURRENT PROTECTION TO BE PER DATA PLATE 2. STRAPS FOR FLEX TO BE SECURE/NEED ANCHORS 3. DISCONNECTS TO HAVE PROPER FRONT - WORKING CLEARANCE 4. ROOFTOP EQUIPMENT TO BE PROPERLY IDENTIFIED ON PANEL SCHEDULE INSPECTION FOR STORE INTERIOR 1. PERMANENT PANEL DIRECTORIES NEEDED - NEC 408.4 2. PLAN SHOWS DISCONNECTS FOR FCI'S 3. NEED 40 AMP CKT TO WH1 4. ALL KITCHEN 120V 20 AMP RECEPTACLES NEED GFI PROTECTION. SPACE IS NOT TO BE OCCUPIED BEFORE APPROVAL |
|
08/10/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
12/19/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* OK CONTINUED USE OF FOUR NEW DISPENSERS MAKE SURE SEAL OFF'S REMAIN ACCEPTABLE. |
|
12/15/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* INSPECTION FOR THE USE OF FOUR NEW FUEL DISPENSER ON SOUTHSIDE ONLY. PROVIDE COMPLIANCE LETTER 1. CHANGE PERMIT TO REFLECT CORRECT ADDRESS (4390 N 1ST AV NOT 4370) 2. INSTALL REQUIRED SEAL OFF'S NEXT TO PUMP 3 AS REQUIRED BY NEC 514.9 OK TO PACK AND POUR. CALL FOR AN INSPECTION FOR THESE FITTINGS NO LATER THAN 12/19/06. MAKE SURE THESE FITTINGS REMAIN ACCESSIBLE NEC 314.29 3. EMERGENCY SHUT OFF TO BE ISOLATED FROM OTHER POWER AND LIGHT CONDUCTORS UNLESS TEMPORARY OK TO USE PUMPS AFTER CORRECTIONS. |
|
12/14/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* HAVE ADDRESS CORRECTED TO PROPER ADDRESS ON PERMIT |
|
12/13/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* NEED REVISED PLAN TO BE APPROVED BY ORIGINAL PLAN REVIEWER. |