Permit: T06CM01004
Permit Details
Apply Date:
02/17/2006
Applicant:
N/A
Description:
TI:CHARTER SCHOOL & SITE
Architects:
- MEYER, JAMES CHAUNCEY
Contractors:
- MEAD MEYER CONSTRUCTION INC
Permit Reviews
Permit Number - T06CM01004
Permit Status: C of o
Permit Description: TI:CHARTER SCHOOL & SITE
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
01/04/2007 | 3RD PARTY REVIEW-REVISION/OTHER | 01/08/2007 | COMPLETED |
02/17/2006 | PLANS OK TO SUBMIT - 3RD PARTY | 03/09/2006 | COMPLETED |
02/17/2006 | PLANS OK TO SUBMIT - SITE | 03/06/2006 | COMPLETED |
03/09/2006 | SITE | 05/04/2006 | COMPLETED |
03/09/2006 | 3RD PARTY REVIEW-COMMERCIAL TI | 06/12/2006 | COMPLETED |
06/09/2006 | RESUBMITTAL - SITE | 07/24/2006 | COMPLETED |
06/12/2006 | POST 3RD PARTY REVIEW | 07/24/2006 | COMPLETED |
07/13/2006 | OTHER | 07/18/2006 | COMPLETED |
07/24/2006 | RESUBMITTAL | 08/02/2006 | COMPLETED |
08/02/2006 | RESUBMITTAL | 11/02/2006 | COMPLETED |
11/16/2006 | 3RD PARTY REVIEW-REVISION/OTHER | 11/30/2006 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T06CM01004
Permit Status: C of o
Permit Description: TI:CHARTER SCHOOL & SITE
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
02/17/2006 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: C of o
Permit Number: T06CM01004
Permit Description: TI:CHARTER SCHOOL & SITE
Total Completed Inspections - 20
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/21/2006 | PLUMBING - PRE SLAB | RMYERS | Approved | 1. ABS DWV UNDERSLAB OK TO COVER 2. WATER TEST ONE RISER TO TEN FEET 3. "K" COPPER LOOPED TO SINK OK 4. REMEMBER 3" C.O REQUIRES 18" CLEARANCE IN FRONT. |
08/21/2006 | PLUMBING - ROUGH, SOIL | RMYERS | Approved | |
10/24/2006 | PLUMBING - ABOVE CEILING | RMYERS | Approved | IVRS - Inspection :* |
10/27/2006 | ELECTRIC - INTERMEDIATE | CCLEMENS | Approved | IVRS - Inspection :* OK WALL COVER I.D.L HALF WALLS, OFFICES BEHIND NORTH BATHROOMS, SW OFFICE WALLS. |
11/06/2006 | FRAMING | AQUIROZ | Approved | IVRS - Inspection :* |
11/21/2006 | PLUMBING - INTERMEDIATE | RMYERS | Approved | IVRS - Inspection :* 1. OK TO COVER ALL AREAS CLOSET FLANGES OK |
11/27/2006 | SHEET ROCK NAILING | AQUIROZ | Approved | IVRS - Inspection :* |
12/19/2006 | MECHANICAL - INTERMEDIATE | JMILITEL | Approved | IVRS - Inspection :* 1. INSULATE ALL SPIRAL DUCTS & SHEETMETAL FITTINGS. 2. SEAL ALL JOINTS ON METAL DUCTS. 3. DUCT SMOKE DETECTORS MUST BE AHEAD OF ALL DUCT INLETS. 4. SUPPORT FLEX DUCTS EVERY 5' & USE 1 1/2" MIN. HANGER STRAP. |
12/19/2006 | BUILDING ABOVE CEILING | AQUIROZ | Approved | IVRS - Inspection :* EXCLUDES LINE 9, LINE K 7.5-9 |
12/19/2006 | ELECTRIC - ABOVE CEILING | CCLEMENS | Approved | IVRS - Inspection :* OK MAIN CEILING AREA ONLY CLOSE UP ALL OPEN J-BOXES FIRST GO THROUGH OTHER CEILING AREAS AND CORRECT AS DISCUSSED. |
12/19/2006 | SIGN - FINAL | JYBARRA | Approved | IVRS - Inspection :* MUST FINAL ELEC IN INSTALLED SIGN T06OT01057 FOR C/O TO BE ISSUED |
12/20/2006 | RIGHT OF WAY - FINAL | MOTERO | Approved | |
12/20/2006 | ENGINEERING - FINAL | MRUSSO | Approved | |
12/28/2006 | MECHANICAL - ABOVE CEILING | JMILITEL | Approved | IVRS - Inspection :* 1) OK CEILING TILES 2) NEED TO SEE AND TEST DUCT SMOKE DETECTORS |
01/03/2007 | PLUMBING - FINAL | RMYERS | Approved | IVRS - Inspection :* PLUMBING FINAL OK OK FOR C OF O S.T.O.I |
01/26/2007 | BUILDING - FINAL | AQUIROZ | Approved | IVRS - Inspection :* OK C OF O |
02/01/2007 | ELECTRIC - FINAL | CCLEMENS | Approved | IVRS - Inspection :* |
02/05/2007 | MECHANICAL - FINAL | JMILITEL | Approved | IVRS - Inspection :* 1) AIR BALANCE OK 2) OK FOR FINAL |
02/12/2007 | FIRE - FINAL | LTHOMAS | Approved | |
02/12/2007 | FIRE SPKLR - FINAL | LTHOMAS | Approved |