Permit Details

Status:
C of o
Type:
COMMERCIAL ALTERATION
Apply Date:
02/17/2006
Applicant:
N/A
Description:
TI:CHARTER SCHOOL & SITE
Architects:
  • MEYER, JAMES CHAUNCEY
Contractors:
  • MEAD MEYER CONSTRUCTION INC

Permit Reviews

Permit Number - T06CM01004
Permit Status: C of o
Permit Description: TI:CHARTER SCHOOL & SITE
Start Date Submittal Complete Date Status  
01/04/2007 3RD PARTY REVIEW-REVISION/OTHER 01/08/2007 COMPLETED Review Details
02/17/2006 PLANS OK TO SUBMIT - 3RD PARTY 03/09/2006 COMPLETED Review Details
02/17/2006 PLANS OK TO SUBMIT - SITE 03/06/2006 COMPLETED Review Details
03/09/2006 SITE 05/04/2006 COMPLETED Review Details
03/09/2006 3RD PARTY REVIEW-COMMERCIAL TI 06/12/2006 COMPLETED Review Details
06/09/2006 RESUBMITTAL - SITE 07/24/2006 COMPLETED Review Details
06/12/2006 POST 3RD PARTY REVIEW 07/24/2006 COMPLETED Review Details
07/13/2006 OTHER 07/18/2006 COMPLETED Review Details
07/24/2006 RESUBMITTAL 08/02/2006 COMPLETED Review Details
08/02/2006 RESUBMITTAL 11/02/2006 COMPLETED Review Details
11/16/2006 3RD PARTY REVIEW-REVISION/OTHER 11/30/2006 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T06CM01004
Permit Status: C of o
Permit Description: TI:CHARTER SCHOOL & SITE
Total Outstanding Activity Conditions - 1
Date Name
02/17/2006 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: C of o
Permit Number: T06CM01004
Permit Description: TI:CHARTER SCHOOL & SITE
Total Completed Inspections - 20
Date Description Inspector Results Comments
08/21/2006 PLUMBING - PRE SLAB RMYERS Approved 1. ABS DWV UNDERSLAB OK TO COVER
2. WATER TEST ONE RISER TO TEN FEET
3. "K" COPPER LOOPED TO SINK OK
4. REMEMBER 3" C.O REQUIRES 18" CLEARANCE IN FRONT.
08/21/2006 PLUMBING - ROUGH, SOIL RMYERS Approved
10/24/2006 PLUMBING - ABOVE CEILING RMYERS Approved IVRS - Inspection :*
10/27/2006 ELECTRIC - INTERMEDIATE CCLEMENS Approved IVRS - Inspection :*
OK WALL COVER I.D.L HALF WALLS, OFFICES BEHIND NORTH BATHROOMS, SW OFFICE WALLS.
11/06/2006 FRAMING AQUIROZ Approved IVRS - Inspection :*
11/21/2006 PLUMBING - INTERMEDIATE RMYERS Approved IVRS - Inspection :*
1. OK TO COVER ALL AREAS
CLOSET FLANGES OK
11/27/2006 SHEET ROCK NAILING AQUIROZ Approved IVRS - Inspection :*
12/19/2006 MECHANICAL - INTERMEDIATE JMILITEL Approved IVRS - Inspection :*
1. INSULATE ALL SPIRAL DUCTS & SHEETMETAL FITTINGS.
2. SEAL ALL JOINTS ON METAL DUCTS.
3. DUCT SMOKE DETECTORS MUST BE AHEAD OF ALL
DUCT INLETS.
4. SUPPORT FLEX DUCTS EVERY 5' & USE 1 1/2" MIN. HANGER STRAP.
12/19/2006 BUILDING ABOVE CEILING AQUIROZ Approved IVRS - Inspection :*
EXCLUDES LINE 9, LINE K 7.5-9
12/19/2006 ELECTRIC - ABOVE CEILING CCLEMENS Approved IVRS - Inspection :*
OK MAIN CEILING AREA ONLY
CLOSE UP ALL OPEN J-BOXES FIRST
GO THROUGH OTHER CEILING AREAS AND CORRECT AS DISCUSSED.
12/19/2006 SIGN - FINAL JYBARRA Approved IVRS - Inspection :* MUST FINAL ELEC IN INSTALLED SIGN T06OT01057 FOR C/O TO BE ISSUED
12/20/2006 RIGHT OF WAY - FINAL MOTERO Approved
12/20/2006 ENGINEERING - FINAL MRUSSO Approved
12/28/2006 MECHANICAL - ABOVE CEILING JMILITEL Approved IVRS - Inspection :*
1) OK CEILING TILES
2) NEED TO SEE AND TEST DUCT SMOKE DETECTORS
01/03/2007 PLUMBING - FINAL RMYERS Approved IVRS - Inspection :*
PLUMBING FINAL OK
OK FOR C OF O S.T.O.I
01/26/2007 BUILDING - FINAL AQUIROZ Approved IVRS - Inspection :*
OK C OF O
02/01/2007 ELECTRIC - FINAL CCLEMENS Approved IVRS - Inspection :*
02/05/2007 MECHANICAL - FINAL JMILITEL Approved IVRS - Inspection :*
1) AIR BALANCE OK
2) OK FOR FINAL
02/12/2007 FIRE - FINAL LTHOMAS Approved
02/12/2007 FIRE SPKLR - FINAL LTHOMAS Approved

Documents

File Name Document Type  
None CONSTRPLANS VIEW
AREAMODWORKSHEET.TIF DOCUMENTS VIEW
None DOCUMENTS VIEW
C OF O_02-13-2007.TIF CERT OF OCC VIEW