Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM01004
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/01/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
01/30/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. EMERGENCY LIGHTING NOT CORRECT - NEC 700.12E 2. PANEL DIRECTORYS TO BE CORRECTLY IDENTIFIED NEC 408.4 3. IDENTIFY ROOFTOP EQUIPMENT |
|
01/17/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. EMERGENCY LIGHTING TO BE INSTALLED PER PLAN AND MEET THE REQUIREMENTS OF NEC 700.12E 2. CONDUCTORS IN AUX. GUTTER TO BE DERATED PER NEC 366.6 3. CORRECTIONS ON ROOF AS DISCUSSED |
|
01/11/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* SERVICE INSPECTION ONLY 1. VERIFY THE SERVICE HAS GROUNDING ELECTRODE OR INSTALL ONE 2. IDENTIFY SERVICE DISCONNECT AND INSTALL ADDRESS ON SERVICE. 3. USE PROPER BOND CLAMPS FOR WATER & GAS BOND. I WOULD LIKE TO INSPECT INTERIOR PANELS NEXT (AND TRANSFORMERS) PLEASE HAVE EQUIPMENT OPEN FOR INSPECTION. |