Permit: T06CM01004

Parcel: 10603079C

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM01004

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/01/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/30/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. EMERGENCY LIGHTING NOT CORRECT - NEC 700.12E
2. PANEL DIRECTORYS TO BE CORRECTLY IDENTIFIED
NEC 408.4
3. IDENTIFY ROOFTOP EQUIPMENT
01/17/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. EMERGENCY LIGHTING TO BE INSTALLED PER PLAN AND MEET THE REQUIREMENTS OF NEC 700.12E
2. CONDUCTORS IN AUX. GUTTER TO BE DERATED PER
NEC 366.6
3. CORRECTIONS ON ROOF AS DISCUSSED
01/11/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
SERVICE INSPECTION ONLY
1. VERIFY THE SERVICE HAS GROUNDING ELECTRODE OR INSTALL ONE
2. IDENTIFY SERVICE DISCONNECT AND INSTALL ADDRESS ON SERVICE.
3. USE PROPER BOND CLAMPS FOR WATER & GAS BOND.

I WOULD LIKE TO INSPECT INTERIOR PANELS NEXT (AND TRANSFORMERS) PLEASE HAVE EQUIPMENT OPEN FOR INSPECTION.