Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/01/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 01/02/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 12/19/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK MAIN CEILING AREA ONLY CLOSE UP ALL OPEN J-BOXES FIRST GO THROUGH OTHER CEILING AREAS AND CORRECT AS DISCUSSED. |
|
| 12/01/2006 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1. REMOVE CEILING TILES 2. PROVIDE INSTALLATION SPECIFICATIONS ON GRID 3. GRID SUPPORT WIRE NOT TO SUPPORT EQUIPMENT 4. SUPPORT WIRES TO BE SECURED AT BOTH ENDS - NO TIE WIRE. 5. FINISH ALL LOW VOLTAGE WIRING AND SUPPORT OFF GRID. |