Permit: T06CM01004

Parcel: 10603079C

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
01/17/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
1. NEW 75KVA TRANS OK INCLUDING GROUNDING
2. INDIVIDUAL PNLS A B C - OK
3. EXISTING GUTTER UNDER PNLS A & B OVER 30 CURRENT CARRYING CONDUCTORS? 59 OR 50
4. PNLC - ISOLATED GROUND - SHOWN ON PLANS BUT NOT EXISTING ON SITE.
5. SERVICE GRN ELECT (NEW) OK, SERVICE ADDRESSED, CLAMPS OK
6. EARTH GRD ON ALARM PNL NOT REQUIRED
7. SANTEC APPROVAL JOEL & MEGETRIC STAMP 881-8896
01/02/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. FINISH WIRING/DEMO ABOVE CEILINGS
2. PROVIDE EARTH GROUND TO ALARM PANEL
3. SUPPORT WIRES FOR EQUIPMENT TO BE INDIVIDUAL GRID SUPPORT WIRES & SECURED AT BOTH ENDS
4. CLOSE ALL J-BOXES
HAVE INSULATION UNDERGROUND SCREW, USE ANCHORS AS LISTED.
5. GO THROUGH EXISTING REAR AREA CEILING AND MAKE SURE IT IS SAFE/NO OPEN WIRING ETC.
10/27/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALL COVER I.D.L HALF WALLS, OFFICES BEHIND NORTH BATHROOMS, SW OFFICE WALLS.
10/20/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
S.W CORRIDOR, S.E AREA WALLS UP TO KITCHEN AREA
10/13/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALL COVER ROOMS - #135, A, B, C, 130, 130B, 120, A20A, 121, 101 A (WEST WALL)
08/22/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER ELECTRICAL IN CORRIDOR - NOTE - THERE IS NO MEAN PROVIDED FOR GROUNDING THESE BOXES AT THIS TIME? ALSO, PLAN SHOWS EMERGENCY LIGHTING IN CORRIDOR.
08/16/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER RACEWAYS UNDER SLAB AFTER CORRECTIONS IN MAX. # OF 90'S MADE
08/15/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
HAVE MAX. 4 90 DEG. BENDS IN UNDERGROUND RUNS OR INSTALL PULL BOX.