Permit: T05CM04615
Permit Details
Apply Date:
09/07/2005
Applicant:
GOLDSTEIN, GENE
Description:
FIRE DAMAGE REPAIR - RESTAURANT
Architects:
- GOLDSTEIN, GENE
Contractors:
- GOLDSTEIN CONSTRUCTION MANAGEMEN
Permit Reviews
Permit Number - T05CM04615
Permit Status: Final
Permit Description: FIRE DAMAGE REPAIR - RESTAURANT
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 04/05/2006 | REVISION - WALK THRU | 04/05/2006 | COMPLETED |
| 04/18/2006 | REVISION - WALK THRU | 04/18/2006 | COMPLETED |
| 09/07/2005 | COMMERCIAL TI | 11/09/2005 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T05CM04615
Permit Status: Final
Permit Description: FIRE DAMAGE REPAIR - RESTAURANT
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 09/07/2005 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T05CM04615
Permit Description: FIRE DAMAGE REPAIR - RESTAURANT
Total Completed Inspections - 16
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/22/2005 | BUILDING - FINAL | LHANLY | Approved | IVRS - Inspection :*MINIMUM 12" TALL ADDRESS DISPLAY REQUIRED. |
| 11/22/2005 | FRAMING | LHANLY | Approved | IVRS - Inspection :* |
| 11/23/2005 | MECHANICAL - HOODS | JMILITEL | Approved | IVRS - Inspection :*EXISTING GREASE DUCTS & SHAFTS OK CONDENSATE FROM A/C UNIT CANNOT TERMINATE INTO A SEWER VENT. RUN DRAIN FROM A/C & MAKE UP AIR UNIT DOWN INTO KITCHEN & TERMINATE INTO THE FLOOR DRAIN. VENT CONNECTOR ON WATER HEATER MUST BE 3" NOT 4". PROVIDE A LOW COMBUSTION AIR VENT IN WATER HEATER ROOM |
| 11/23/2005 | RIGHT OF WAY - FINAL | PWHIDDON | Approved | PER EMAIL |
| 11/23/2005 | FIRE - KITCHEN EXH HOOD FINAL | LLAKEY | Approved | A PLAN & PERMIT IS REQUIRED FOR HOOD |
| 11/30/2005 | SIGN - FINAL | JYBARRA | Approved | IVRS - Inspection :* |
| 12/07/2005 | ENGINEERING - FINAL | NKALAHAR | Approved | BOTTOM OF HANDICAPPED PARKING SIGN NEEDS TO BE AT 84" |
| 01/10/2006 | MECHANICAL - INTERMEDIATE | JMILITEL | Approved | IVRS - Inspection :* 1) ON FINAL FINISH CONNECTING MAKE UP AIR UNIT |
| 01/10/2006 | ELECTRIC - FINAL | RMAJUTA | Approved | PER INSP CARD |
| 01/10/2006 | ELECTRIC - INTERMEDIATE | RMAJUTA | Approved | IVRS - Inspection :* ELECTRICAL CONTRACTOR WORK FINISHED MECH LV CONNECTION TO BE BY MECH. CONTRACTOR |
| 05/22/2006 | PLUMBING - ABOVE CEILING | RRICH | Approved | IVRS - Inspection :* UNDERGROUND ROUGH SOIL OK PROVIDE PIPE WRAPS THRU CONCRETE. 1. PROVIDE P-TRAP ON INDIRECT DRAIN FROM SANITIZER BOWL WITH CLEANOUT FOR OVER 5'. 2. PROVIDE 1/4" PER FOOT FALL ON TRAP ARM OF 2-COMPS OF 3 COMP SINK. 3. VENT FROM FLOW CONTROL TO BE PER PLAN. 4. HAND SINK SHALL HAVE LONG RADIUS DRAINAGE FITTINGS. 5. VENT FROM WATER HEATER TO BE 2' ABOVE TOP OF PARAPET WHEN WITHIN 8' 15 PSI TEST FROM METER THRU NO ANSUL VALVE INSTALLED NOW. |
| 05/25/2006 | PLUMBING - INTERMEDIATE | RRICH | Approved | IVRS - Inspection :* APPROVED PER APPROVED PLAN. |
| 05/25/2006 | PLUMBING - GAS PRESSURE TEST | RRICH | Approved | IVRS - Inspection :* |
| 06/01/2006 | PLUMBING - FINAL | RRICH | Approved | IVRS - Inspection :* RECEIVED (2) IN HOUSE BACKFLOW CERTIFICATIONS (1) FOR ICE MAKER (1) FOR CARBONATOR (ONLY) |
| 06/06/2006 | MECHANICAL - FINAL | JMILITEL | Approved | IVRS - Inspection :* OK FOR FINAL |
| 06/07/2006 | FIRE - FINAL | LLAKEY | Approved |