Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T05CM04615

Parcel: 12801047A


Addresses:

6135 E 22ND ST

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
05/25/2006 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
05/24/2006 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
05/22/2006 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
1. SUPPORT GAS PIPING AT APPLIANCE LINE.
2. INSTALL ANSUL VALVE & RETEST MAX 5 PSI.
3. INSTALL CORRECT RATED FLEXES & VALVES AT ALL APPLIANCES AT FUTURE.
05/19/2006 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
NO ACCESS 9:43
01/24/2006 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*MET WITH CONTRACTOR & ARCHITECT ON SITE TO TRY TO POINT THEM IN CORRECT DIRECTION. SEE ALL NOTES PLEASE
PROVIDE TEST GAUGE IN 1/10 POUND INCREMENTS WITH MINIMUM TEST PRESSURE WITH NO LOSS FOR 15 MINUTES
PROVIDE CORRECT SUPPORTS FOR ALL PIPING. PROVIDE AGA OR CSA APPROVED VALVES AT ALL LOCATIONS ONLY 2 PSI ON PROVIDE CORRECT RATED FLEX FOR ROOF TOP UNIT SYSTEM AT THIS TIME
01/12/2006 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PLEASE PROVIDE A FLOOR PLAN OF EXISTING BLDG SHOWING ALL PLUMBING FIXTURES WITH GAS ISOMETRIC
2) THERE ARE SEVERAL PLUMBING FIXTURES THAT APPEAR TO BE ADDED WITHOUT PERMITS
3) THERE ARE MANY ITEMS TAHT DON'T MEET ANY CODE COMPLIANCE INCLUDING IMPROPER VENTING OF WATER HEATER
4) GAS PIPING NOT INSTALLED PER APPROVED PLAN
5) GAS PIPING SHALL REQUIRE REVISED GAS ISOMETRIC WITH LOCATION ON ANSUL GAS VALVE
5) PLAN DOES NOT SUPPLY ENOUGH INFORMATION FOR COMPLETE LIST