Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/25/2006 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* | |
| 05/24/2006 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* | |
| 05/22/2006 | PLUMBING - GAS PRESSURE TEST | Partial Approval | IVRS - Inspection :* 1. SUPPORT GAS PIPING AT APPLIANCE LINE. 2. INSTALL ANSUL VALVE & RETEST MAX 5 PSI. 3. INSTALL CORRECT RATED FLEXES & VALVES AT ALL APPLIANCES AT FUTURE. |
|
| 05/19/2006 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* NO ACCESS 9:43 |
|
| 01/24/2006 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999*MET WITH CONTRACTOR & ARCHITECT ON SITE TO TRY TO POINT THEM IN CORRECT DIRECTION. SEE ALL NOTES PLEASE PROVIDE TEST GAUGE IN 1/10 POUND INCREMENTS WITH MINIMUM TEST PRESSURE WITH NO LOSS FOR 15 MINUTES PROVIDE CORRECT SUPPORTS FOR ALL PIPING. PROVIDE AGA OR CSA APPROVED VALVES AT ALL LOCATIONS ONLY 2 PSI ON PROVIDE CORRECT RATED FLEX FOR ROOF TOP UNIT SYSTEM AT THIS TIME |
|
| 01/12/2006 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PLEASE PROVIDE A FLOOR PLAN OF EXISTING BLDG SHOWING ALL PLUMBING FIXTURES WITH GAS ISOMETRIC 2) THERE ARE SEVERAL PLUMBING FIXTURES THAT APPEAR TO BE ADDED WITHOUT PERMITS 3) THERE ARE MANY ITEMS TAHT DON'T MEET ANY CODE COMPLIANCE INCLUDING IMPROPER VENTING OF WATER HEATER 4) GAS PIPING NOT INSTALLED PER APPROVED PLAN 5) GAS PIPING SHALL REQUIRE REVISED GAS ISOMETRIC WITH LOCATION ON ANSUL GAS VALVE 5) PLAN DOES NOT SUPPLY ENOUGH INFORMATION FOR COMPLETE LIST |