Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - HOODS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/23/2005 | MECHANICAL - HOODS | Approved | IVRS - Inspection :*EXISTING GREASE DUCTS & SHAFTS OK CONDENSATE FROM A/C UNIT CANNOT TERMINATE INTO A SEWER VENT. RUN DRAIN FROM A/C & MAKE UP AIR UNIT DOWN INTO KITCHEN & TERMINATE INTO THE FLOOR DRAIN. VENT CONNECTOR ON WATER HEATER MUST BE 3" NOT 4". PROVIDE A LOW COMBUSTION AIR VENT IN WATER HEATER ROOM |