Permit: T05CM04615

Parcel: 12801047A


Addresses:

6135 E 22ND ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
06/01/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
RECEIVED (2) IN HOUSE BACKFLOW CERTIFICATIONS (1) FOR ICE MAKER (1) FOR CARBONATOR (ONLY)
05/31/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
FLUSH CAP URINAL TO AVOID HAZARD.
SEE NOTE #5
05/25/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. PROVIDE VACUUM BREAKERS AT THE HOSE BIB LOCATIONS.
2. CAP URINAL PIPING AND REMOVE OR HAVE CORRECT INSTALL WITH THIS FIXTURE REFLECTED ON APPROVED PLAN.
3. HAVE SODA DISPENSING EQUIPMENT INSTALLED AND PROVIDE BACKFLOW CERTIFICATIONS.
4. SERVICE EXPANSION TANK.
5. SEPARATE ICE BIN DRAIN FROM MAKER DRAIN AND PROVIDE FULL SIZE BIN DRAIN.