Permit: T05CM04615

Parcel: 12801047A


Addresses:

6135 E 22ND ST

Inspection Status: Approved

Inspection History: PLUMBING - ABOVE CEILING

Date Description Inspector Results Comments
05/22/2006 PLUMBING - ABOVE CEILING Approved IVRS - Inspection :*
UNDERGROUND ROUGH SOIL OK
PROVIDE PIPE WRAPS THRU CONCRETE.
1. PROVIDE P-TRAP ON INDIRECT DRAIN FROM SANITIZER BOWL WITH CLEANOUT FOR OVER 5'.
2. PROVIDE 1/4" PER FOOT FALL ON TRAP ARM OF 2-COMPS OF 3 COMP SINK.
3. VENT FROM FLOW CONTROL TO BE PER PLAN.
4. HAND SINK SHALL HAVE LONG RADIUS DRAINAGE FITTINGS.
5. VENT FROM WATER HEATER TO BE 2' ABOVE TOP OF PARAPET WHEN WITHIN 8'
15 PSI TEST FROM METER THRU NO ANSUL VALVE INSTALLED NOW.
05/19/2006 PLUMBING - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
01/24/2006 PLUMBING - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
01/12/2006 PLUMBING - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*