Permit Details

Status:
Expired
Type:
COMMERCIAL ALTERATION
Apply Date:
06/28/2005
Applicant:
N/A
Description:
TI: REMODELING ADDING A COMPUTER ROOM, ADDITIONAL MECHANICAL EQUIPMENT FOR ROOM WHICH REQUIRES A NEW ELECTRICAL SERVICE.
Contractors:
  • DAKOTA INTERNET PATRNERS INC
  • MEANS DESIGN AND BUILDING CORPOR

Permit Reviews

Permit Number - T05CM03164
Permit Status: Expired
Permit Description: TI: REMODELING ADDING A COMPUTER ROOM, ADDITIONAL MECHANICAL EQUIPMENT FOR ROOM WHICH REQUIRES A NEW ELECTRICAL SERVICE.
Start Date Submittal Complete Date Status  
06/28/2005 PLANS OK TO SUBMIT - COMM 07/18/2005 COMPLETED Review Details
07/18/2005 COMMERCIAL TI 08/24/2005 COMPLETED Review Details
08/29/2005 RESUBMITTAL 08/29/2005 COMPLETED Review Details
09/06/2005 RESUBMITTAL 09/07/2005 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T05CM03164
Permit Status: Expired
Permit Description: TI: REMODELING ADDING A COMPUTER ROOM, ADDITIONAL MECHANICAL EQUIPMENT FOR ROOM WHICH REQUIRES A NEW ELECTRICAL SERVICE.
Total Outstanding Activity Conditions - 2
Date Name
06/28/2005 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.
08/04/2005 SPECIAL INSPECTION FOR EPOXY ANCHORS IS REQUIRED.

Outstanding Inspections

Permit Status: Expired
Permit Number: T05CM03164
Permite Description: TI: REMODELING ADDING A COMPUTER ROOM, ADDITIONAL MECHANICAL EQUIPMENT FOR ROOM WHICH REQUIRES A NEW ELECTRICAL SERVICE.
Total Outstanding Inspections - 10
Last Inspection Date Description Inspector Results Comments
EXCAVATION/LAYOUT REBAR & ZON N/A Not Inspected
ELECTRIC - TEMPORARY SERVICE N/A Not Inspected
03/23/2006 ELECTRIC - CABLE DROP N/A Not ready for Inspection IVRS - Inspection :*
03/23/2006 ELECTRIC - SERVICE UPGRADE N/A Not ready for Inspection IVRS - Inspection :*
03/23/2006 ELECTRIC - FINAL N/A Not ready for Inspection IVRS - Inspection :*
MEET WITH CONTRACTOR TO DISCUSS JOB
04/16/2006 ELECTRIC - CONSTRUCTION POWER N/A Partial Approval IVRS - Inspection :*
1) RECEIVED CHECK #301 FOR #108.00 AFTER HOURS INSPECTION
2) SUPPORT SEAL TITE AT BOARD
3) BOND JUMPERS TO BE AS PER 250.102
4) IDENTIFY CONDUCTORS AT LUGS
5) BOND #115 ENCLOSURE
04/18/2006 ELECTRIC - UNDERGROUND N/A Partial Approval IVRS - Inspection :*
11/17/2005 ELECTRIC - INTERMEDIATE N/A Not ready for Inspection IVRS - Inspection :*WIRING AND METHODS NOT AS TO PLANS-INSTALL AS PER PLANS OR REVISE PLANS
USE OF FLEXABLE CORDS TO MEET REQUIREMENTS OF 400.7
12/13/2005 BUILDING - FINAL N/A Partial Approval IVRS - Inspection :*PROVIDE ELECTRIC FINAL INSP. REPORT AND PLUMBING FINAL
ALL STRUCTURAL OK
YOU MAY LEAVE INSP CARD AT FRONT DESK FOR FINAL
12/19/2005 PLUMBING - FINAL N/A Not ready for Inspection IVRS - Inspection :*REMOVE FURNCO AND MAKE SOLVENT WELD CONNECTION
CONDENSATE DRAIN MUST BE OFF APPROVED MAT'LS, MAY NOT COMBINE WITH ANY OTHER DRAIN, AND MAY NOT BE REDUCED IN SIZE
T & P RELIEF MAY NOT DUMP INTO LAV TAILPIECE.

Completed Inspections

Permit Status: Expired
Permit Number: T05CM03164
Permit Description: TI: REMODELING ADDING A COMPUTER ROOM, ADDITIONAL MECHANICAL EQUIPMENT FOR ROOM WHICH REQUIRES A NEW ELECTRICAL SERVICE.
Total Completed Inspections - 11
Date Description Inspector Results Comments
10/05/2005 FRAMING AQUIROZ Approved IVRS - Inspection :*
11/17/2005 SHEET ROCK NAILING AQUIROZ Approved IVRS - Inspection :*
11/17/2005 BUILDING ABOVE CEILING AQUIROZ Approved IVRS - Inspection :*
11/17/2005 PLUMBING - PROGRESS RRICH Approved IVRS - Inspection :*
11/17/2005 PLUMBING - INTERMEDIATE RRICH Approved IVRS - Inspection :*
11/17/2005 FIRE - FINAL LTHOMAS Approved
11/17/2005 FIRE SPKLR - FINAL LTHOMAS Approved
11/18/2005 MECHANICAL - FINAL CWILLIAM Approved IVRS - Inspection :*A/C COOLED EQUIPMENT RM. FOR COMPUTERS
11/18/2005 MECHANICAL - ABOVE CEILING CWILLIAM Approved IVRS - Inspection :*
11/18/2005 MECHANICAL - INTERMEDIATE CWILLIAM Approved IVRS - Inspection :*
06/01/2006 TEP CLEARANCE - AM JWEATHER Approved ECO CLEARED FOR UNIT #111 PER R. HOLLANDER

Documents

File Name Document Type  
None CONSTRPLANS VIEW
None DOCUMENTS VIEW