Permit: T05CM03164
Permit Details
Status:
Expired
Type:
COMMERCIAL ALTERATION
Address:
4003 E SPEEDWAY BL #111
Address NEW:
4003 E SPEEDWAY BL #111
Apply Date:
06/28/2005
Applicant:
N/A
Description:
TI: REMODELING ADDING A COMPUTER ROOM, ADDITIONAL MECHANICAL EQUIPMENT FOR ROOM WHICH REQUIRES A NEW ELECTRICAL SERVICE.
Contractors:
- DAKOTA INTERNET PATRNERS INC
- MEANS DESIGN AND BUILDING CORPOR
Permit Reviews
Permit Number - T05CM03164
Permit Status: Expired
Permit Description: TI: REMODELING ADDING A COMPUTER ROOM, ADDITIONAL MECHANICAL EQUIPMENT FOR ROOM WHICH REQUIRES A NEW ELECTRICAL SERVICE.
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 06/28/2005 | PLANS OK TO SUBMIT - COMM | 07/18/2005 | COMPLETED |
| 07/18/2005 | COMMERCIAL TI | 08/24/2005 | COMPLETED |
| 08/29/2005 | RESUBMITTAL | 08/29/2005 | COMPLETED |
| 09/06/2005 | RESUBMITTAL | 09/07/2005 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T05CM03164
Permit Status: Expired
Permit Description: TI: REMODELING ADDING A COMPUTER ROOM, ADDITIONAL MECHANICAL EQUIPMENT FOR ROOM WHICH REQUIRES A NEW ELECTRICAL SERVICE.
Total Outstanding Activity Conditions - 2
| Date | Name |
|---|---|
| 06/28/2005 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
| 08/04/2005 | SPECIAL INSPECTION FOR EPOXY ANCHORS IS REQUIRED. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T05CM03164
Permite Description: TI: REMODELING ADDING A COMPUTER ROOM, ADDITIONAL MECHANICAL EQUIPMENT FOR ROOM WHICH REQUIRES A NEW ELECTRICAL SERVICE.
Total Outstanding Inspections - 10
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| EXCAVATION/LAYOUT REBAR & ZON | N/A | Not Inspected | ||
| ELECTRIC - TEMPORARY SERVICE | N/A | Not Inspected | ||
| 03/23/2006 | ELECTRIC - CABLE DROP | N/A | Not ready for Inspection | IVRS - Inspection :* |
| 03/23/2006 | ELECTRIC - SERVICE UPGRADE | N/A | Not ready for Inspection | IVRS - Inspection :* |
| 03/23/2006 | ELECTRIC - FINAL | N/A | Not ready for Inspection | IVRS - Inspection :* MEET WITH CONTRACTOR TO DISCUSS JOB |
| 04/16/2006 | ELECTRIC - CONSTRUCTION POWER | N/A | Partial Approval | IVRS - Inspection :* 1) RECEIVED CHECK #301 FOR #108.00 AFTER HOURS INSPECTION 2) SUPPORT SEAL TITE AT BOARD 3) BOND JUMPERS TO BE AS PER 250.102 4) IDENTIFY CONDUCTORS AT LUGS 5) BOND #115 ENCLOSURE |
| 04/18/2006 | ELECTRIC - UNDERGROUND | N/A | Partial Approval | IVRS - Inspection :* |
| 11/17/2005 | ELECTRIC - INTERMEDIATE | N/A | Not ready for Inspection | IVRS - Inspection :*WIRING AND METHODS NOT AS TO PLANS-INSTALL AS PER PLANS OR REVISE PLANS USE OF FLEXABLE CORDS TO MEET REQUIREMENTS OF 400.7 |
| 12/13/2005 | BUILDING - FINAL | N/A | Partial Approval | IVRS - Inspection :*PROVIDE ELECTRIC FINAL INSP. REPORT AND PLUMBING FINAL ALL STRUCTURAL OK YOU MAY LEAVE INSP CARD AT FRONT DESK FOR FINAL |
| 12/19/2005 | PLUMBING - FINAL | N/A | Not ready for Inspection | IVRS - Inspection :*REMOVE FURNCO AND MAKE SOLVENT WELD CONNECTION CONDENSATE DRAIN MUST BE OFF APPROVED MAT'LS, MAY NOT COMBINE WITH ANY OTHER DRAIN, AND MAY NOT BE REDUCED IN SIZE T & P RELIEF MAY NOT DUMP INTO LAV TAILPIECE. |
Completed Inspections
Permit Status: Expired
Permit Number: T05CM03164
Permit Description: TI: REMODELING ADDING A COMPUTER ROOM, ADDITIONAL MECHANICAL EQUIPMENT FOR ROOM WHICH REQUIRES A NEW ELECTRICAL SERVICE.
Total Completed Inspections - 11
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/05/2005 | FRAMING | AQUIROZ | Approved | IVRS - Inspection :* |
| 11/17/2005 | SHEET ROCK NAILING | AQUIROZ | Approved | IVRS - Inspection :* |
| 11/17/2005 | BUILDING ABOVE CEILING | AQUIROZ | Approved | IVRS - Inspection :* |
| 11/17/2005 | PLUMBING - PROGRESS | RRICH | Approved | IVRS - Inspection :* |
| 11/17/2005 | PLUMBING - INTERMEDIATE | RRICH | Approved | IVRS - Inspection :* |
| 11/17/2005 | FIRE - FINAL | LTHOMAS | Approved | |
| 11/17/2005 | FIRE SPKLR - FINAL | LTHOMAS | Approved | |
| 11/18/2005 | MECHANICAL - FINAL | CWILLIAM | Approved | IVRS - Inspection :*A/C COOLED EQUIPMENT RM. FOR COMPUTERS |
| 11/18/2005 | MECHANICAL - ABOVE CEILING | CWILLIAM | Approved | IVRS - Inspection :* |
| 11/18/2005 | MECHANICAL - INTERMEDIATE | CWILLIAM | Approved | IVRS - Inspection :* |
| 06/01/2006 | TEP CLEARANCE - AM | JWEATHER | Approved | ECO CLEARED FOR UNIT #111 PER R. HOLLANDER |