Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/08/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. CANNOT STACK LUGS 2. BOND JUMPERS TO BE SIZED FOR 250.122 |
|
| 05/31/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 05/24/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK BONDING JUMPERS |
|
| 05/19/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. BONDING JUMPERS LINE SIDE TO BE AS PER 250.102 & 250.66 2. PLEASE PROVIDE A LETTER FOR TORQUE VALVES OF PIN ADAPTOR CONNECTIONS. |
|
| 05/12/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* PROVIDE MANUFACTURERS INSTRUCTIONS AND LABELING FOR PIN ADAPTORS. |
|
| 05/10/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. PROVIDE A SEALING DEVICE FOR ENTRANCES ABOVE CURRENT CARRING PARTS. 2. FINISH TERMINATIONS AND BONDING NOTE 250.102 & 250.66 OK CONDUITS FOR SERVICE |
|
| 04/18/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK 4-2" PVC PULL BOX TO WALL OK PREVIOUS ITEMS |
|
| 03/23/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 11/17/2005 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :*WIRING AND METHODS NOT AS TO PLANS-INSTALL AS PER PLANS OR REVISE PLANS USE OF FLEXABLE CORDS TO MEET REQUIREMENTS OF 400.7 |