Permit: T05CM03164

Parcel: 12213035B

Inspection Status: Partial Approval

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
09/08/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. CANNOT STACK LUGS
2. BOND JUMPERS TO BE SIZED FOR 250.122
05/31/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
05/24/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK BONDING JUMPERS
05/19/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. BONDING JUMPERS LINE SIDE TO BE AS PER 250.102 & 250.66
2. PLEASE PROVIDE A LETTER FOR TORQUE VALVES OF PIN ADAPTOR CONNECTIONS.
05/12/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
PROVIDE MANUFACTURERS INSTRUCTIONS AND LABELING FOR PIN ADAPTORS.
05/10/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. PROVIDE A SEALING DEVICE FOR ENTRANCES ABOVE CURRENT CARRING PARTS.
2. FINISH TERMINATIONS AND BONDING
NOTE 250.102 & 250.66
OK CONDUITS FOR SERVICE
04/18/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK 4-2" PVC PULL BOX TO WALL
OK PREVIOUS ITEMS
03/23/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
11/17/2005 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*WIRING AND METHODS NOT AS TO PLANS-INSTALL AS PER PLANS OR REVISE PLANS
USE OF FLEXABLE CORDS TO MEET REQUIREMENTS OF 400.7