Permit: T05CM03164

Parcel: 12213035B

Inspection Status: Partial Approval

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
03/07/2007 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
T&P TO EXTERIOR IS OK
WH NOT SHOWN ON PLAN. PLAN NOT APPROVED
WH IN CEILING MISSING DRAIN PAN AND EXPANSION TANK
WASHER BOX DRAIN FOR CONDENSATE BEHIND SODA MACHINE REQUIRES
1. AN APPROVED PLAN
2. APPROVED FITTINGS
3. PIPE SUPPORTS
4. TEST
12/19/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*REMOVE FURNCO AND MAKE SOLVENT WELD CONNECTION
CONDENSATE DRAIN MUST BE OFF APPROVED MAT'LS, MAY NOT COMBINE WITH ANY OTHER DRAIN, AND MAY NOT BE REDUCED IN SIZE
T & P RELIEF MAY NOT DUMP INTO LAV TAILPIECE.
12/13/2005 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
1) SHALL PROVIDE A PERM CAP ON WASTE LINE. DO NOT COVER
11/17/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*PROVIDE TERMINATION OF 1 1/4 CONDENSATE DRAW INTO LAV TAILPIECE AND CAP OFF 2" DRAIN FROM STAND PIPE RECEPTOR