Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T05CM03164
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/29/2005 | DAN CASTRO | ZONING | REVIEW | Approved | |
| 08/29/2005 | DROBEY1 | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show the location and arrangement of the outside air supply components to the air handlers on the drawing. 2. Show the location of the duct smoke detectors on the drawing. |
| 08/29/2005 | DROBEY1 | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 08/29/2005 | DROBEY1 | PLUMBING-COMMERCIAL | REVIEW | Denied | Show that the receptor of the condensate drain and the evaporative cooler drain complies with Section 804.1, UPC 1994, (e.g. readily accessible, shape and capacity to prevent splashing, and with an airbreak for the drains) |