Review Date Reviewer's Name Type of Review Description Status Comments
08/29/2005 DAN CASTRO ZONING REVIEW Approved
08/29/2005 DROBEY1 MECHANICAL-COMMERCIAL REVIEW Denied 1. Show the location and arrangement of the outside air supply components to the air handlers on the drawing.
2. Show the location of the duct smoke detectors on the drawing.
08/29/2005 DROBEY1 ELECTRICAL-COMMERCIAL REVIEW Approved
08/29/2005 DROBEY1 PLUMBING-COMMERCIAL REVIEW Denied Show that the receptor of the condensate drain and the evaporative cooler drain complies with Section 804.1, UPC 1994, (e.g. readily accessible, shape and capacity to prevent splashing, and with an airbreak for the drains)