Permit: T04CM02430
Permit Details
Status:
C of o
Type:
COMMERCIAL NEW
Address:
8620 E TANQUE VERDE RD
Address NEW:
8620 E TANQUE VERDE RD
Apply Date:
05/28/2004
Applicant:
N/A
Description:
NEW:FIRE STATION 21
Contractors:
- SUNDT CORP ,
Permit Reviews
Permit Number - T04CM02430
Permit Status: C of o
Permit Description: NEW:FIRE STATION 21
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 01/24/2005 | REVISION | 01/24/2005 | COMPLETED |
| 05/28/2004 | PLANS OK TO SUBMIT - COMM | 05/28/2004 | COMPLETED |
| 05/28/2004 | COMMERCIAL NEW | 06/30/2004 | COMPLETED |
| 08/05/2004 | RESUBMITTAL | 08/19/2004 | COMPLETED |
| 08/20/2004 | RESUBMITTAL | 08/26/2004 | COMPLETED |
| 08/26/2004 | RESUBMITTAL | 09/08/2004 | COMPLETED |
| 09/08/2004 | RESUBMITTAL | 09/10/2004 | COMPLETED |
| 09/10/2004 | RESUBMITTAL | 11/02/2004 | COMPLETED |
| 12/07/2004 | REVISION | 01/03/2005 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T04CM02430
Permit Status: C of o
Permit Description: NEW:FIRE STATION 21
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 05/28/2004 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: C of o
Permit Number: T04CM02430
Permit Description: NEW:FIRE STATION 21
Total Completed Inspections - 43
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/13/2004 | STEM WALL/RETAINING WALL | RSUBA | Approved | IVRS - Inspection :*/TRASH ENCLOSURE |
| 10/26/2004 | PLUMBING - INTERMEDIATE | JSTANLEY | Approved | IVRS - Inspection :*/2" VENT TO 2ND FLOOR THRU ROOF MECH. EQUIP ROOM. NEED NEW DETAIL ON WASHER BOX. |
| 11/01/2004 | PLUMBING - YARD WTR LINE/TEST | RRICH | Approved | IVRS - Inspection :*/2" T/L COPPER FROM METER THRU BACKFLOW DEVICE TO BUILDING SERVICE VALVE ON INTERIOR WATER TEST OK. |
| 11/19/2004 | ELECTRIC - UFER | RHOLLAND | Approved | IVRS - Inspection :*/ 1) OK TO CLEAR CONSTRUCTION POWER |
| 11/30/2004 | EXCAVATION/LAYOUT REBAR & ZON | HLEYVA | Approved | IVRS - Inspection :*/ 1) OK TOP OUT AT GRID LINE H FROM 3 TO 5 AND ? H FROM 3 TO 2 TO 16'-8" |
| 12/02/2004 | ELECTRIC - CONSTRUCTION POWER | RHOLLAND | Approved | OK FOR CONSTRUCTION POWER - CLEARED BY PHONE |
| 12/02/2004 | TEP CLEARANCE - PM | BGRANT | Approved | CLEARED BY PHONE PER RICK HOLLANDER |
| 12/09/2004 | REINFORCED MASONRY PRE-GROUT | HLEYVA | Approved | IVRS - Inspection :* |
| 12/13/2004 | ELECTRIC - UNDERGROUND | RHOLLAND | Approved | IVRS - Inspection :OK FOR CORRECT ENCASEMENT AND BACK FILL PVC CONDUITS UNDER APPARATUS BAYS SUBJECT TO LATER OR PLAN REVISION WITH APPROVED PLAN CHECK STAMP OK PVC CONDUITS SOUTHEAST SIDE OF PROJECT & NORTHEAST - OUTSIDE |
| 12/17/2004 | ROOF NAILING | HLEYVA | Approved | IVRS - Inspection :*/OK @ APARATUS ROOM |
| 12/29/2004 | BUILDING PRE-SLAB | BSTEVENS | Approved | IVRS - Inspection :* |
| 12/30/2004 | PLUMBING - ROUGH, SOIL | RMYERS | Approved | NOT READY - NOT INSTALLED PER PLAN - PLAN CALLS FOR 4" SDR 35 INSTALLED IS 3" ABS AT OUTLET OF SEPARATOR. |
| 01/19/2005 | PLUMBING - ROOF DRAINS | RRICH | Approved | IVRS - Inspection :* 3" RWL & OF RWL WATER TEST OK. |
| 02/04/2005 | SHEET ROCK NAILING | BSTEVENS | Approved | IVRS - Inspection :* APPROVED |
| 03/08/2005 | MECHANICAL - ABOVE CEILING | JMILITEL | Approved | IVRS - Inspection :* ADD MORE BANDS OR FINE WRAP. NO COMBUSTIBLES ALLOWED WITHIN 18" OF SIDE OF HOOD & CHECK STOVE MANUFACTURERS CLEARANCES |
| 03/10/2005 | BUILDING ABOVE CEILING | BSTEVENS | Approved | IVRS - Inspection :* APPROVED |
| 03/16/2005 | MECHANICAL - HOODS | JMILITEL | Approved | IVRS - Inspection :* |
| 03/16/2005 | MECHANICAL - INTERMEDIATE | JMILITEL | Approved | IVRS - Inspection :* |
| 03/16/2005 | TEP CLEARANCE - AM | JKOZUCH | Approved | ECO |
| 03/24/2005 | MECHANICAL - FINAL | JMILITEL | Approved | IVRS - Inspection :* OK FOR FINAL C OF O |
| 03/24/2005 | RIGHT OF WAY - FINAL | PWHIDDON | Approved | |
| 03/25/2005 | FIRE - FINAL | LLAKEY | Approved | |
| 03/25/2005 | FIRE - KITCHEN EXH HOOD FINAL | LLAKEY | Approved | |
| 03/25/2005 | FIRE SPKLR - FINAL | LLAKEY | Approved | |
| 03/25/2005 | FIRE SPKLR - OH PIPING & HYDRO | LLAKEY | Approved | |
| 03/25/2005 | FIRE SPKLR - UG PIPING FLUSH | LLAKEY | Approved | |
| 03/25/2005 | FIRE SPKLR - UG, PIPING, HYDRO | LLAKEY | Approved | |
| 03/30/2005 | NPPO - FINAL | ACONNOR | Approved | |
| 03/30/2005 | LANDSCAPE - FINAL | ACONNOR | Approved | |
| 04/01/2005 | PLUMBING - FINAL | JSTANLEY | Approved | PLEASE HAVE PLUMBER INSULATE WATER AT WASH RACK. BBQ HAS BEEN REMOVED & CAPPED OFF |
| 04/01/2005 | SIGN - FINAL | DCAPPLE | Approved | OK FOR TEMPORARY C OF 0 ONLY. |
| 04/01/2005 | PLUMBING - GAS PRESSURE TEST | JSTANLEY | Approved | |
| 04/01/2005 | PLUMBING - PROGRESS | JSTANLEY | Approved | |
| 04/01/2005 | EXT METAL CLIPS/EXT SHEATHING | BSTEVENS | Approved | |
| 04/01/2005 | FRAMING | BSTEVENS | Approved | |
| 04/01/2005 | U VALUE FOR WINDOW | BSTEVENS | Approved | |
| 04/01/2005 | BUILDING - PROGRESS | BSTEVENS | Approved | |
| 04/01/2005 | BUILDING - FINAL | BSTEVENS | Approved | IVRS - Inspection :* |
| 04/01/2005 | ELECTRIC - FINAL | RHOLLAND | Approved | IVRS - Inspection :* |
| 04/01/2005 | ELECTRIC - ABOVE CEILING | RHOLLAND | Approved | IVRS - Inspection :* |
| 04/01/2005 | ELECTRIC - INTERMEDIATE | RHOLLAND | Approved | IVRS - Inspection :* |
| 05/03/2005 | ENGINEERING - FINAL | DROBERTS | Approved | |
| 05/05/2005 | PLUMBING - GAS PRESS TEST FNL | JSTANLEY | Approved | IVRS - Inspection :*NO PERMIT CARD ON JOB |