Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/01/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/28/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* PARTIAL I WITNESSED GENERATOR TEST. PAPER WORK IS FORTH COMING. 1) FINISH PREVIOUS ELECTRICAL ITEM | |
| 03/25/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK TEMP C OF O FOR TRAINING AND OPERATIONAL SET UP |
|
| 03/23/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) GENERATOR SIGNAGE IS NEEDED PER 700.8. 2) INSTALL GROUNDING ELECTRODE SYSTEM FOR GENERATOR. 3) FINISH SUMP PUMP SYSTEM. 4) POLE BASE GROUNDING AND POWER FINISH. 5) FINISH PREVIOUS ITEMS. ROOF: 1) UNIT DISCONNECTS NEED LABELING | |
| 03/22/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED APPROVED EXTENDER RINGS 370-20/314.20 2) SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING AT 2X2 FIXTURES | |
| 03/15/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 03/14/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) CANNOT STACK LUGS. 2) CLEAN SURFACE UNDER LUGS. 3) BONDING JUMPERS TO BE SIZED PER 250-102 & 250.66 LIVE SIDE 250-102 & 250.122 LOAD SIZE. OK FEEDER TO MAIN BREAKERS CONTRACTOR IS MAINTAINING LOCK G?/TAG OUT. | |
| 02/22/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* PARTIAL |