Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T04CM02430
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/23/2004 | Robert Sherry | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the water piping to coordinate with the revised water calculations. Coordinate the riser diagram with the plumbing plan. 2. Provide the civil drawing referenced in floor plan 1/P1.1 to show the routing of the building sewer. (Note: The site utility drawings for Activities T04OT01064 and T04BU01265 are not coordinated with the current plumbing drawings for water and building sewer.) |
| 08/23/2004 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 08/25/2004 | SEPTIC APPROVAL | WWM | REVIEW | Denied | septic system not yet approved. plans must be revised to show septic. (site & plumbing) (P04CP09495 & P04CP09494) |
| 08/26/2004 | EGRANT1 | BUILDING-COMMERCIAL | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/26/2004 | BETH GRANT | OUT TO CUSTOMER | Completed |