Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T04CM02430
Parcel: 11449037G

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04CM02430
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/09/2004 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied 1. An atmospheric vacuum breaker is not appropriate for use with an ice machine due to the valves downstream of the vacuum breaker. If the ice machine is equipped with pumps for water control, a reduced pressure backflow preventer will be required. Reference Section 603.2, UPC 1994.
2. Revise the water piping to coordinate with the revised water calculations. Coordinate the riser diagram with the plumbing plan.
3. Provide upper terminal cleanout for the pumped drain from the wash rack. Reference Section 710.7, UPC 1994.
4. Comment not addressed. Provide roof drainage calculations along with the sizes of the roof drains, overflows, and rain leaders.
5. Coordinate keynote #16 on sheet P1.1 with the current design and make keynote #20 legible.
6. Provide the civil drawing referenced in floor plan 1/P1.1 to show the routing of the building sewer.
08/09/2004 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the ventilation calculations for FCU-3 to comply with the requirements of Section 403.3.2, IMC 2000.
08/10/2004 GERRY KOZIOL WWM REVIEW Denied Needs to build public sewer. Need to show location/method of connection to public sewer. Cannot drain exterior wash rack to public sewer (need to remove from above fees when deleted from dwgs). Needs wastewater IWC review - Tom Tomchak, 579-5771.
08/13/2004 Doug Laakso BUILDING-COMMERCIAL REVIEW Denied .. T04CM02430 .. 8620 E TANQUE VERDE ROAD .. DGL .. 8/19/04 ..
.. 2ND REVIEW

S1. See prior comment #5 , revise calculations for masonry to reflect 2000 IBC criteria , as requested.
S2. Provide on drawings soils requirements, showing extent of excavation and backfill, as well as , criteria for backfill soils and compaction for structure.
S3. Indicate on drawings soils special inspection requirements.
08/18/2004 DAVID RIVERA ZONING REVIEW Approved
08/19/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/19/2004 TAMI ACHONG OUT TO CUSTOMER Completed
08/19/2004 ANGIE SHOFFSTALL REJECT SHELF Approved