Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T04CM02430
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/08/2004 | Linda Buczynski | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT LBUCZYN1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS. 1. Lighting fixture P3 on Sheet E1.U is not the same fixture called out on Sheet E1.1. Approved plans are based on the Luminaire Schedule on Sheet E1.1. Please clarify and correct. 2. Please plot the City of Tucson fiber optic Communications on Sheet E1.U. See Sheet TC1.0. This would be consistent with Fire Station 20. And the communications conduit runs very close to the telephone run, and should be plotted on the same sheet to enable better field coordination of possible conflicts. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/10/2004 | BETH GRANT | OUT TO CUSTOMER | Completed |
| 09/10/2004 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |