Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T00CM04303
Permit Details
Apply Date:
08/30/2000
Applicant:
METRO PERMIT EXPRESS
Description:
NEW:RETAIL SHELL
Architects:
- MORROW, KEVIN THOMAS
Contractors:
- R A S BUILDERS
Permit Reviews
Permit Number - T00CM04303
Permit Status: Final
Permit Description: NEW:RETAIL SHELL
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
05/07/2001 | REVISION | 05/22/2001 | COMPLETED |
05/22/2001 | REVISION | 05/30/2001 | COMPLETED |
06/27/2001 | REVISION | 06/29/2001 | COMPLETED |
08/30/2000 | 3RD PARTY REVIEW-COMMERCIAL | 02/13/2001 | COMPLETED |
Completed Inspections
Permit Status: Final
Permit Number: T00CM04303
Permit Description: NEW:RETAIL SHELL
Total Completed Inspections - 25
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/16/2001 | PLUMBING - ROUGH, SOIL | RMYERS | Approved | IVRS - Inspection 0000* |
02/20/2001 | ELECTRIC - UFER | DWITT | Approved | IVRS - Inspection 0000* UFER OK ( TO BE SIZED BY ELEC. INSP |
02/26/2001 | STEM WALL/RETAINING WALL | DWITT | Approved | IVRS - Inspection 0000* |
03/08/2001 | BUILDING PRE-SLAB | DWITT | Approved | IVRS - Inspection 0000* |
03/08/2001 | EXCAVATION/LAYOUT REBAR & ZON | DWITT | Approved | IVRS - Inspection 0000* STEMS APPROVED |
04/02/2001 | ROOF NAILING | DWITT | Approved | IVRS - Inspection 0000* |
04/02/2001 | EXT METAL CLIPS/EXT SHEATHING | DWITT | Approved | IVRS - Inspection 0000* |
04/05/2001 | REINFORCED MASONRY PRE-GROUT | DWITT | Approved | IVRS - Inspection 0000* |
04/23/2001 | FRAMING | DWITT | Approved | IVRS - Inspection 0000* 1) CORRECT SHINERS 2) COMPLETE HDWE 3) RESHOOT OSB WHERE OVER DRIVEN OR MISSED 4) REBLOCK OSB AS NEEDED |
04/24/2001 | ELECTRIC - INTERMEDIATE | RMAJUTA | Approved | IVRS - Inspection 0000* WALLS AND CEILING SHELL |
05/04/2001 | PLUMBING - SEWER HCS CONNECT | RMYERS | Approved | IVRS - Inspection 0000* |
05/11/2001 | STUCCO MESH | DWITT | Approved | IVRS - Inspection 0000* FINISH NAILING |
06/11/2001 | PLUMBING - FINAL | RMYERS | Approved | IVRS - Inspection 0000* |
06/11/2001 | PLUMBING - PROGRESS | RMYERS | Approved | IVRS - Inspection 0000*1)SMITH WEST 2" WATTS #162485 CERTIFICATION OK.2)NORTH-WATTS 009MZ #21855,WATTS 009MZ #21369 CERTIFICATION OK. 3)PLUMBING FINAL OK "SHELL" ONLY. |
06/19/2001 | ELECTRIC - UNDERGROUND | JORTA | Approved | IVRS - Inspection 0000*1)NEED ACCURATE PLANS-MOSTLY AT SEWER.2)ADD GUTTER TO 800 AMP SERVICE.3)NEED LOCK.4)NEED GROUNDING BUSHING AND BOND JUMPER.5)STRESS TIE TERMINATION CAN PER DIAGRAM.6)NEED WATER BOND.*1 OWNER PANEL.7)WILL NEED BOND POSTED AND ALL INSPECTION TO SIGN OFF.8)REVISION SHOWS SERVICE AT B IS REVISED ON PLAN-MUST BE ACCURATE. |
06/19/2001 | SHEET ROCK NAILING | DWITT | Approved | IVRS - Inspection 0000* |
06/19/2001 | U VALUE FOR WINDOW | DWITT | Approved | IVRS - Inspection 0000* |
06/19/2001 | BUILDING ABOVE CEILING | DWITT | Approved | IVRS - Inspection 0000* |
07/13/2001 | ELECTRIC - FINAL | JORTA | Approved | IVRS - Inspection 0000*APPROVED FOR SERVICE A BOND OWNER PANEL. SERVICE "B" PENDING LETTER FOR LASHING REQUIREMENT. |
07/13/2001 | BUILDING - FINAL | DWITT | Approved | IVRS - Inspection 0000* |
09/07/2001 | ENGINEERING - FINAL | DROBERTS | Approved | |
09/18/2001 | FIRE SPKLR - OH PIPING & HYDRO | FIRE | Approved | |
09/18/2001 | ELECTRIC - CABLE DROP | JORTA | Approved | |
09/18/2001 | ELECTRIC - SERVICE RELOCATION | JORTA | Approved | |
10/31/2001 | PERMIT FINALED | FIRE | Approved |