Inspection History: ENGINEERING - FINAL

Permit Number - T00CM04303

Inspection Description - ENGINEERING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/07/2001 ENGINEERING - FINAL Approved
08/01/2001 ENGINEERING - FINAL Denied 1.) HANDICAP VERTICAL PARKING SIGNS DO NOT MEET THE 7-FOOT CLEARANCE AS SPECIFIED IN DETAIL 2 ON SHEET DP.1. 2.) THE EXISTING MASONRY WALLS HAVE NOT BEEN RAISED TO THE 6-FOOT HEIGHT AS SPECIFIED ON SHEET DP.2. DURING THE ON-SITE INSPECTION IT HAS BEEN NOTED THAT NORTH AND NORTHWEST WALLS ARE RETAINING WALLS WITH APPROXIMATELY 3-FEET OF SOIL BEING RETAINED AT THIS TIME. THE STRUCTURAL INTEGRITY OF THE WALLS ARE IN QUESTION AT THIS TIME, AND ADDING THE ADDITIONAL MATERIAL MAY NOT BE POSSIBLE WITHOUT CHANGING THE CURRENT DESIGN. 3.) MINOR PONDING OF WATER HAS BEEN NOTED ON THE NORTH SIDE OF THE RAISED ISLAND ADJACENT TO THE CATCH BASIN LOCATED ON THE SOUTH SIDE OF LOT #2. CHANGES SHOULD BE MADE TO THE PAVEMENT TO ALLOW DRAINAGE TO THE INLET SIDE OF THIS BASIN.