Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - PROGRESS
Permit Number - T00CM04303
Inspection Description - PLUMBING - PROGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/11/2001 | PLUMBING - PROGRESS | Approved | IVRS - Inspection 0000*1)SMITH WEST 2" WATTS #162485 CERTIFICATION OK.2)NORTH-WATTS 009MZ #21855,WATTS 009MZ #21369 CERTIFICATION OK. 3)PLUMBING FINAL OK "SHELL" ONLY. |
|
05/17/2001 | PLUMBING - PROGRESS | Partial Approval | IVRS - Inspection 0000* 1) OVER HEAD COPPER OK HOSE BIBBS OK OK TO COVER 2) ROOF DRAINS OK WATER TEST OK 3)PLEASE REDLINE PER RFI 14 (ADDITIONAL ROOF DRAINS).4)IF THERE IS AN APPROVED C.O. ADPT UNDER F.P.C.O. COVER OK TO POUR CONCRETE (FRANK PATTERN CLEAN OUT). | |
05/15/2001 | PLUMBING - PROGRESS | Not ready for Inspection | IVRS - Inspection 0000* | |
05/04/2001 | PLUMBING - PROGRESS | Partial Approval | IVRS - Inspection 0000* 1) BLDG SEWER FROM CLEAN OUT TO MAIN OK 2) TIE IN TO EXSISTING OK 3) TRANSISTION FITTINGS OK 4) OK TO BACKFILL 5) HOSE BIBB CONNECTIONS IN COLUMNS (2) OK |
|
04/24/2001 | PLUMBING - PROGRESS | Partial Approval | IVRS - Inspection 0000* 1) COPPER WATER PIPING IN NORTH BLDG OK PRESSURE TEST OK 2) REFER TO TABLE 3-1 1 1/2" COPPER AND SMALLER 6' MAX HANGERS 3) OK TO COVER WALLS ON NORTH BLDG | |
04/13/2001 | PLUMBING - PROGRESS | Partial Approval | IVRS - Inspection 0000* 1) ROOF DRAINS AND OVER FLOWS ON NORTH WING OK WATER TEST OK 2) OK TO COVER |
|
04/05/2001 | PLUMBING - PROGRESS | Partial Approval | IVRS - Inspection 0000* 1) HOSE BIBBS IN COLUMNS (2 PLACES) IN NORTH BLDG OK CONTRACTOR TO VERIFY PRESSURE TEST 2) SLEEVE FOR BLDG SERVICE OK | |
03/08/2001 | PLUMBING - PROGRESS | Partial Approval | IVRS - Inspection 0000* 1) ROOF DRAINS IN STEM WALL ON WEST SIDE OF BLDG OK, DEPENDING ON WATER TEST IN FUTURE. 2) OK TO POUR STEM WALL TAKE CARE WHEN POURING | |
03/07/2001 | PLUMBING - PROGRESS | Denied | IVRS - Inspection 0999* 1) JOB CLOSED DUE TO RAIN |