Permit: T00CM04303


Addresses:

910 W IRVINGTON RD


Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T00CM04303

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Approved

Date Description Inspector Results Comments
06/19/2001 ELECTRIC - UNDERGROUND Approved IVRS - Inspection 0000*1)NEED ACCURATE PLANS-MOSTLY AT SEWER.2)ADD GUTTER TO 800 AMP SERVICE.3)NEED LOCK.4)NEED GROUNDING BUSHING AND BOND JUMPER.5)STRESS TIE TERMINATION CAN PER DIAGRAM.6)NEED WATER BOND.*1 OWNER PANEL.7)WILL NEED BOND POSTED AND ALL INSPECTION TO SIGN OFF.8)REVISION SHOWS SERVICE AT B IS REVISED ON PLAN-MUST BE ACCURATE.
05/18/2001 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*5-4" PVC CONDUIT BURIAL,
INSTALLATION APPROVED-TO BUILD.-A- (UP TO ISLAND-AT TRANSFORMER END).SUBJECT TO APPROVED PLANS.
05/08/2001 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000* OK 3-4" PVC TRANSFORMER TO BLDG, OK 5-4" PVC SOUTH OF TRANSFORMER 20'
04/26/2001 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000* SECONDARY'S
03/14/2001 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000* LARGER BLDG 2 1/2" FEEDER STUBS 10 AND 1 1/4" TILE STUBS APPROVED AND COMPLETE. SUBJECT TO CITY APPROVED REVISION ON SERVICE LOCATION CHANGES
03/12/2001 ELECTRIC - UNDERGROUND Partial Approval FEEDER STUBS AND TILE STUBS 2 1/2 AND 1 1/4 RESPECTIVLY APPROVED FOR COLUMN LINE "M" COMPLETE