Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T00CM04303
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/13/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*APPROVED FOR SERVICE A BOND OWNER PANEL. SERVICE "B" PENDING LETTER FOR LASHING REQUIREMENT. | |
07/09/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1.ONE 60 AMP MISSING IN OWNER MAIN DISCONNECT 2.) HOLE UNER GUTTER 1 1/4" STILL OPEN? | |
07/06/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*1.) RETERMINATE BLUE PHASE LINE SIDE ALL ALUM STRANDS TO GO INTO LUG CHECK ALL OTHERS 2.) USE A ROMEX CONNECTOR TO CLOSE OFF HOLE WHERE GROUND ENTER BOTTOM CT CAN 3.) SEAL 1 1/2" HOLE BOTTOM NORTH GUTTER. SER B 1.) BLACK PHASE SEC SIDE 2 CONDUCTORS SOME STANDS OFF ALL NEED TO BE IN LUG. | |
06/29/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* | |
06/19/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* | |
05/17/2001 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000*NEED CITY APPROVED REVISED PLAN ON SHELL PERMIT.NEED ACCURATE ONE LINE ELECTRICAL.NEED ACCURATE PLAN ELECTRICAL.ALL SUBSEQUANT T.I.PLANS THERE WILL AUTOMATICALLY BE ACCURATE. | |
03/12/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* SUBJECT TO APPROVED PLANS ON BLDG SERVICE LOCATIONS NEED CITY REVISION |