Permit: T00CM02201
Permit Details
Apply Date:
05/01/2000
Applicant:
REICHERT BOB
Description:
REMODEL:CARPORTS TO ROOMS (3) T00VL00104
Contractors:
- LONGHORN CONSTRUCTION
Permit Reviews
Permit Number - T00CM02201
Permit Status: C of o
Permit Description: REMODEL:CARPORTS TO ROOMS (3) T00VL00104
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 05/09/2001 | RESUBMITTAL | 10/10/2001 | STOPPED |
| 07/24/2000 | COMMERCIAL NEW | 01/12/2001 | COMPLETED |
| 11/09/2000 | SITE | 05/09/2001 | COMPLETED |
| 11/09/2000 | COMMERCIAL NEW | 05/10/2001 | STOPPED |
| 12/23/2002 | REVISION | 12/23/2002 | COMPLETED |
Completed Inspections
Permit Status: C of o
Permit Number: T00CM02201
Permit Description: REMODEL:CARPORTS TO ROOMS (3) T00VL00104
Total Completed Inspections - 27
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/26/2001 | PLUMBING - INTERMEDIATE | JSTANLEY | Approved | IVRS - Inspection 0000* |
| 07/25/2001 | BUILDING PRE-SLAB | EMONAHAN | Approved | IVRS - Inspection 0000$@ SIDE S SIDE UNIT. |
| 08/27/2001 | EXCAVATION/LAYOUT REBAR & ZON | EMONAHAN | Approved | IVRS - Inspection 0000* |
| 09/19/2001 | ROOF NAILING | EMONAHAN | Approved | |
| 09/26/2001 | FRAMING | EMONAHAN | Approved | IVRS - Inspection 0000* |
| 10/16/2001 | STUCCO MESH | EMONAHAN | Approved | IVRS - Inspection 0000* |
| 11/02/2001 | STEM WALL/RETAINING WALL | EMONAHAN | Approved | IVRS - Inspection 0000* |
| 12/07/2001 | ELECTRIC - UNDERGROUND | RHOLLAND | Approved | IVRS - Inspection 0000* |
| 12/13/2001 | PLUMBING - YARD WTR LINE/TEST | JSTANLEY | Approved | IVRS - Inspection 0000*PA OK TO COVER CALL WHEN READY FOR 2ND PHASE.PA OK TO COVER 1ST PLACE CALL WHEN READY FOR 2ND COVER WATER LINE WITH CLEAN FILL FOR 12" |
| 12/13/2001 | ELECTRIC - TEMPORARY SERVICE | RMAJUTA | Approved | OK TO CLEAR FOR CONST USE.1.) PANEL A TO BE LOCKED OUT BY CONTRACTOR 2.) PANEL B OK TO USE FOR CONSTRUCTION USE ONLY NO INSIDE WIRING TO BE ENERGIZED W/O INSPECTORS APPROVAL ONLY GFI'S BELOW PANEL. |
| 12/22/2001 | ELECTRIC - INTERMEDIATE | RHOLLAND | Approved | IVRS - Inspection 0000*1.) PLEASE INSTALL BATH FANS FOR INSPECTION 2. JUNCTION BOX BELOW PANEL IN WORKING CLEARENCE VIOLATION 110-26. BOX NOT ASSCOCATED WITH ELECTICAL OK WALLS EXCEPT BATHROOM CEILING. |
| 02/14/2002 | SHEET ROCK NAILING | AMATHIES | Approved | IVRS - Inspection 0000*GET REVISION STATING SUBSTITUTION OF DUCT WRAP IN LIEU OF DUCT CHASE FRAMING & DRY WALL. |
| 10/29/2002 | MECHANICAL - FINAL | JMILITEL | Approved | IVRS - Inspection 0999*NO INSPECTION HAVE EVER BEEN CALLED FOR MECHANICAL REMOVE CEILING TILES KITCHEN REMOVE INSULATION LAYING ON TOP OF HOOD. REMOVE DUCT WRAP FROM GREASE DUCT EXPOSE WATER HEATER VENT. PROVIDE EQUIPMENT SCHEDULE NOT SHOWN ON PLANS. RAISE SEWER VENTS 2' ABOVE ANY AIR INTAKE INTO BLDG. PROVIDE A ROOF JACK ON WATER HEATER VENT PROVIDE AN OUTSIDE AIR VENT CONDENSATE CANNOT BE DRILLED IN THE SIDE OF A WASTE VENT WHERE IS EXHAUST & SUPPLY FOR LAUNDRY ROOM ? PROVIDE COMBUSTION AIR VENTS. |
| 10/29/2002 | LANDSCAPE - FINAL | PGILBERT | Approved | Ok for temp C of O. Bike rack is required per site plan. Parking lot striping completion per site plan. Complete decomposed granite per landscape plan; all bare ground is required to be covered with groundcover (ie decomposed granite). Canopy tree are required in the Street landscape border (3 trees per plan). Trash bin required. |
| 10/29/2002 | BUILDING - FINAL | AMATHIES | Approved | IVRS - Inspection 0000* |
| 10/30/2002 | FIRE - FINAL | LTHOMAS | Approved | PLANS AND PERMIT REQUIRED FOR INSTALLATION OF KITCHEN HOOD FIRE EXTINGUISHING SYSTEM. |
| 12/30/2002 | PLUMBING - FINAL | JSTANLEY | Approved | IVRS - Inspection 0000*OK S.T.O.I LAS INSP. ON JOB PLEASE PROVIDE GAS CARDS. |
| 12/30/2002 | PLUMBING - PROGRESS | JSTANLEY | Approved | |
| 12/30/2002 | PLUMBING - GAS PRESSURE TEST | JSTANLEY | Approved | |
| 12/30/2002 | PLUMBING - ABOVE CEILING | JSTANLEY | Approved | |
| 12/30/2002 | PLUMBING - ROUGH, SOIL | JSTANLEY | Approved | |
| 12/30/2002 | ELECTRIC - FINAL | RHOLLAND | Approved | IVRS - Inspection 0999*1.) WHERE IS DISCONNECTING MEANS FOR WATER HEATER? UNIT "A" 2.) PROTECT BULB ON CLOSETS LIGHT 3.) PANELS/DISCONNECTING MEANS FOR WATER HEATER TO HAVE WORKING SPACE & CLEARENCE PER 110-26 UNIT"B" 4.) FILL UNUSED OPENING IN PANEL "B" 5.) USE AN ANTIOXIDE COMPOUND WITH ALUMINUM CONDUCTORS PANEL "B" 6.) MISSING A COVER PLATE IN CLOSET. 7.) TIGHTEN LOOSE FITTINGS AT A/C UNITS. 8.) OUTDOOR LIGHT TO MEET TUCSON LIGHTING CODE SECTION #5. 9.) FINISH ITEM #1,3,4,6 &8 OF PREVIOUS INSPECTION. |
| 01/17/2003 | MECHANICAL - HOODS | CWILLIAM | Approved | IVRS - Inspection 0000* |
| 01/21/2003 | MECHANICAL - ABOVE CEILING | CWILLIAM | Approved | |
| 01/21/2003 | MECHANICAL - INTERMEDIATE | CWILLIAM | Approved | |
| 01/21/2003 | ELECTRIC - ABOVE CEILING | RMAJUTA | Approved | |
| 01/30/2003 | PERMIT FINALED | AMATHIES | Approved |