Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 01/17/2002 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 12/22/2001 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*1.) PLEASE INSTALL BATH FANS FOR INSPECTION 2. JUNCTION BOX BELOW PANEL IN WORKING CLEARENCE VIOLATION 110-26. BOX NOT ASSCOCATED WITH ELECTICAL OK WALLS EXCEPT BATHROOM CEILING. |
| 12/12/2001 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*PARTIAL KITCHEN & MANAGERS OFFICE. |
| 12/07/2001 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*OK DATA INTRENCH OK WALL SOUTH BUILDING EXCEPT PANEL WALL.2.) SMOKE DETECTORS NEED TO BE INSTALLED AS PER MANFACTURES LISTING THEY ARE POSITIONED CLOSE TO CEILING FAN. |
| 09/26/2001 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*1.) ALL JUNCTION BOXES TO BE ACCESS ABLE. 2.) STRAP NM CABLE AND PROTECT AS PER CODE. 3.) PLEASE HAVE A LETTER FROM LICENSED ELECTRICAL (L-11) CONTRACTOR. TO VERIFY WORK BEING DONE JOB REQUIRES LICENSED L-11 ELECTRICAL CONTRACTOR. 5 DAY FOLLOW UP. |